EB 5207 EN
5-1
Installation
5
Installation
5.1 Installation conditions
Work position
If not described otherwise in the valve or
actuator documentation, the work position
for the thermostat is the front view looking
onto the operating controls.
Mounting position
The valve can be mounted in any desired
position.
5.2
Preparation for installation
Before mounting, make sure the following
conditions are met:
−
The thermostat is not damaged.
Proceed as follows:
Lay out the necessary material and tools to
have them ready during mounting.
Risk of damage and impaired functioning
of the frost protection thermostat.
Î
Do not use the frost protection thermostat
together with corrosive media.
Î
Do not bend the capillary (bending
radius
≥
5 mm).
Î
Mount the housing as close to the point
of measurement as possible since the
capillary is sensitive along its entire
length.
NOTICE
!
The temperature at the housing must be at
least as high as the adjusted temperature,
but not higher than +55 °C.
5.3 Mounting the frost
protection thermostat
Wall mounting
1. Unscrew the enclosure cover.
2. Fasten the bottom section of the housing
onto the wall.
3. Route and secure the capillary.
Mounting clamps are required (not included
in the scope of delivery) to position the
capillary properly at the outlet of the heating
battery.
Note
Note
Содержание 5312-2
Страница 4: ...4 EB 5207 EN...
Страница 12: ...2 2 EB 5207 EN...
Страница 20: ...6 2 EB 5207 EN...
Страница 22: ...7 2 EB 5207 EN...
Страница 24: ...8 2 EB 5207 EN...
Страница 26: ...9 2 EB 5207 EN...
Страница 28: ...10 2 EB 5207 EN...
Страница 30: ...11 2 EB 5207 EN...
Страница 32: ...12 2 EB 5207 EN Removal...
Страница 34: ...13 2 EB 5207 EN...
Страница 36: ...14 2 EB 5207 EN...
Страница 40: ...16 2 EB 5207 EN...
Страница 41: ......
Страница 42: ......
Страница 43: ......