EB 2178 EN
Design and principle of operation
Table 2:
Technical data
Type 2432 Valve
Type 43-8
Type 43-8 N
Valve size
DN 15
K
VS
coefficient
2.5
Pressure rating
PN 25
PN 16
Max. perm. differential pressure Δp
20 bar
6 bar
Max. permissible valve temperature
130 °C
120 °C
Type 2430 Control Thermostat
Set point range
45 to 65 °C
Capillary tube
2 m (5 m as special version)
Max. perm. temperature at the sensor
30 K above the adjusted set point
Max. perm. temperature at the set point
adjuster
35 °C
Perm. pressure at sensor
PN 40
Type 2438 Hydraulic Controller
Required differential pressure (pressure loss)
across the control unit on the cold water side
0.4 bar with a tapping rate up to 10 l/minute
0.5 bar with a tapping rate up to 20 l/minute
Pressure rating
PN 16
Idle temperature
Approx. 8 K (optional 15 K) below the adjusted set
point
Min. temperature difference between flow
temperature and temperature set point
10 K
Max. flow rate
20 l/minute
Содержание 43-8