16
EB 3930 EN
Malfunctions
7 Malfunctions
Depending on the operating conditions, check the valve at certain intervals to prevent possi-
ble failure before it can occur. Operators are responsible for drawing up an inspection and
test plan.
Faults
Possible reasons
Recommended action
Solenoid valve does not switch
Spool in the enclosure is
blocked
Contact SAMSON.
Insufficient pilot pressure
Check the pressure line.
Check the pressure line for leak-
age.
Use a larger cross-section for
the pressure line.
The solenoid valve leaks to the
atmosphere
O-rings slipped
Check that the O-rings are cor-
rectly seated.
Pilot pressure is insufficient and
an intermediate position is
reached (air is constantly vent-
ed)
Check the pressure line.
Check the pressure line for leak-
age.
Use a larger cross-section for
the pressure line.
Содержание 3930
Страница 1: ...Translation of original instructions EB 3930 EN Edition October 2020 Type 3930 Solenoid Valve...
Страница 18: ...18 EB 3930 EN...
Страница 19: ...EB 3930 EN 19...