2.5
List of ESD parameters
The ESD parameters can be found in the positioner under
Code 49
.
16
EB 8388-1 EN
ESD functions
Code
No.
Parameters – display
,
Values [default settings]
Description
Note!
The positioner settings cannot be changed unless the ESD code has been entered under
Code 3, see section 1.3.2.
Modifications in Codes 1 and 49 can only be made when the positioner is in ESD Man
operating mode.
0
Operating mode
MAN – AUtO – SAFE – ESd (–> ESd
Man/ESd Auto) – ESC, [MAN]
AUtO:
Automatic operation
MAN:
Manual operation
SAFE:
Fail-safe position
ESd Man: Manual ESD mode
Starting the partial stroke test manually,
see section 2.1.1
ESd Auto: Automatic ESD mode
1
Manual w
0 to 100 [0] % of the nominal range
Adjust the manual set point with the rotary pushbutton.
The current travel/angle is displayed in % when the
positioner is initialized. Otherwise the sensor position in
relation to the central axis is indicated in degrees °.
3
Unlocking the positioner,
configuration
OFF – ON – ESC, [OFF]
The positioner settings cannot be changed on site unless
the ESD code has been entered.
49
ESD parameters
d0 Time until the next automatic
ESD test
Display only.
Time remaining until the next ESD test is started.
d1 Auto test time
1 to 56280 h, [1 h]
Desired time for repeating an ESD test
d2 Step start
0.0 to 100.0 %, [95.0 %]
Start value for step response
d3 Step end
0.0 to 100.0 %, [90.0 %]
End value for step response
d4 Activation of the ramp function
On – Off, [Off]
Activates or deactivates the ramp function.
d5 Ramp time (rising)
0 to 1000 s, [value determined
during initialization, minimum
value: 15 s]
Ramp time for 0 to 100 % (rising) of the ramp function.
A suitable value is determined during initialization; if
possible, make sure the ramp time does not fall below
this value.