background image

test parameter indicates the time that re-
mains until the next test is started.
The positioner alternately displays
“ESd”, the

Manual reference variable w,

and “MAN“.

At the end of the test, the

Status of ESD test

indicates whether the partial stroke test has
been completed successfully or not (see sec-
tion 2.2 “Analyzing measured data“).

2.1.1 On-site operation

Note!

Parameters can only be changed in
positioners in ESD version after entering the
enabling ESD code (Code 3). You can only
change the reading direction (Code 2) if the
ESD code has not been entered.

The described settings can be adjusted di-
rectly on the positioner on site:

4

Entering the ESD code using Code 3

4

Selecting the ESD Man/ESD Auto oper-
ating mode using Code 0

The following modifications can only be per-
formed when the positioner is in ESD Man
operating mode:

4

Setting the reference variable

Manual w

using Code 1

4

Setting the ESD parameters using
Code 49 (see section 2.5)

Starting the partial stroke test:

1. Select operating mode ESD using

Code 0.

2. In operating mode ESD, select

ESD Man

mode, holding down the rotary
pushbutton until the countdown has
elapsed. The test will start.

Note!

Section 2.5 lists the available ESD pa-

rameters.

2.2

Analyzing measured data

TROVIS-VIEW 3:

[Diagnosis > Emergency

Shut Down > Analysis of measured data]

Analyses of the last three partial stroke tests
completed are saved in the positioner with a
time stamp.

If the test has not been completed success-
fully, the reason why the test was cancelled
is indicated under “Maintenance alarm“.
The positioner indicates “ESd tEst FAIL“. Pos-
sible reasons for cancellation depending on
the defined cancellation conditions are:

4

x cancellation: The valve position fell be-
low the

x control value.

EB 8388-1 EN

13

ESD functions

Содержание 3730-3 ESD

Страница 1: ...ectropneumatic Positioner Type 3730 3 ESD Version With HART communication Mounting and Operating Instructions EB 8388 1 EN Firmware version 1 4x Edition November 2006 Fig 1 ESD mode in SAMSON TROVIS V...

Страница 2: ...ting the diagnostic ESD log 7 2 ESD functions 8 2 1 Changing ESD parameters and starting the partial stroke test 12 2 1 1 On site operation 13 2 2 Analyzing measured data 13 2 2 1 Condensed state Faul...

Страница 3: ...s active the positioner keeps the attached valve to a set position e g open The valve does not per form any control tasks anymore In AUTO operating mode the positioner can be used to control the attac...

Страница 4: ...ording to sched ule ESD Auto Partial stroke test The partial stroke test integrated into the positioner can prevent a normally open valve or a valve in its end position from seizing up or getting jamm...

Страница 5: ...ositioner 1 3 1 Converting TROVIS VIEW 3 The TROVIS VIEW 3 version must match the software version of the positioner When establishing communication or ex changing data between the PC and the position...

Страница 6: ...ng mode The ESD code can be found on page 21 Remove the code or make it unreadable to prevent unauthorized use Entering the code on the positioner Default OFF Turn Code 3 Press Turn ON Press Display s...

Страница 7: ...ion Select Print in the File menu to add further information 1 In the File menu select Print Options to choose the scope of the diagnostic log After installing updating the TROVIS VIEW software custom...

Страница 8: ...SD mode parameter in the Diagnosis folder under Emergency Shut Down is set to On In ESD mode the safety shut off valve is specifically moved to the set point of the valve working range parameter Requi...

Страница 9: ...before the test starts Starting from the Step start position pos 2 the valve moves to the defined end position Step end parameter pos 3 The valve re mains in this position for the time defined by the...

Страница 10: ...ction Fig 2 right The ramp function is active when the Activa tion of the ramp function parameter is set to On Note A step before the partial stroke test can be prevented by allocating the value of th...

Страница 11: ...e value falls below the adjusted valve position range 10 to 110 The condition is only active when Activa tion x control is set to On 4 y control value The test is cancelled when the value falls below...

Страница 12: ...s ESd the Manual reference variable w and MAN 5 Set the parameters in the Emergency Shut Down folder as desired The further course of action depends on whether the test is to be started manually Test...

Страница 13: ...when the positioner is in ESD Man operating mode 4 Setting the reference variable Manual w using Code 1 4 Setting the ESD parameters using Code 49 see section 2 5 Starting the partial stroke test 1 Se...

Страница 14: ...ead time s 4 T63 s 4 T98 s 4 Rise time s 4 Settling time s 2 2 1 Condensed state Fault alarm output The Fault alarm output parameter allows you to define which type of alarm is issued by the hardware...

Страница 15: ...easured values of the parame ters determined during the partial stroke test are listed in the Measured data folder 2 4 Resetting ESD TROVIS VIEW 3 Diagnosis Emergency Shut Down Reset ESD Using the Res...

Страница 16: ...l angle is displayed in when the positioner is initialized Otherwise the sensor position in relation to the central axis is indicated in degrees 3 Unlocking the positioner configuration OFF ON ESC OFF...

Страница 17: ...0 0 0 The test is cancelled when the valve position falls below this value E2 Activation y control On Off Off Activates or deactivates y monitoring Activation only makes sense when the partial stroke...

Страница 18: ...led x values outside the toler ance band occurred F5 Max test time exceeded Test not completed within the maximum test duration and therefore cancelled F6 Test manually cancelled Test cancelled by the...

Страница 19: ...no further settings need to be entered EB 8388 1 EN 19 EXPERT test functions Operating mode Code 0 EXPERT functions Test requirements AUtO As in EB 8388 EN MAN ESD mode ESD Man Data logger Statistica...

Страница 20: ...the con trol system and the asset management sys tem As shown in Fig 4 no solenoid valve is re quired since the positioner similar to the so lenoid valve is certified for safe shutdown When the energy...

Страница 21: ...tegrated into the positioner terminals 81 82 is used to gether with an existing external solenoid valve to trigger the data logger EB 8388 1 EN 21 Notes on applications ESD code 1732 24 V 4 20 mA 81 8...

Страница 22: ...22 EB 8388 1 EN...

Страница 23: ...EB 8388 1 EN 23...

Страница 24: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de EB 8388 1 EN 2007 01...

Отзывы: