EB 8065 EN
5-1
Installation
5
Installation
The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.
5.1
Installation conditions
Work position
The work position for the control valve is the
front view looking onto the operating con-
trols (including valve accessories).
Plant operators must ensure that, after instal-
lation of the device, the operating personnel
can perform all necessary work safely and
easily access the device from the work posi-
tion.
Pipeline routing
The inlet and outlet lengths (see Table 5-1)
vary depending on several variables and
process conditions and are intended as rec
-
ommendations. Contact SAMSON if the
lengths are significantly shorter than the rec-
ommended lengths.
To ensure that the valve functions properly,
proceed as follows:
Î
Observe the inlet and outlet lengths (see
Table 5-1). Contact SAMSON if the
valve conditions or states of the medium
process deviate.
Î
Install the valve free of stress and with the
least amount of vibrations as possible.
Read ‘Mounting position’ and ‘Support
or suspension’ in this section.
Î
Install the valve allowing sufficient space
to remove the actuator and valve or to
perform service work on them.
Mounting position
Generally, we recommend installing the
valve with the actuator upright and on top of
the valve.
In the following versions, the valve
must
be
installed with the actuator on top:
−
Valves in DN 100 and larger
−
Valves with insulating section for low
temperatures below –10 °C
Î
Contact SAMSON if the mounting posi-
tion is not as specified above.
Support or suspension
The plant engineering company is
responsible for selecting and implementing a
suitable support or suspension of the
installed control valve and the pipeline.
Depending on the valve version and mount-
ing position, the valve, actuator and pipeline
must be supported or suspended.
Î
Valves, which are not installed in the
pipeline in the upright position with the
actuator on top, must be supported or
suspended.
Valve accessories
Î
During connection of valve accessories,
make sure that they are easily accessible
and can be operated safely from the
work position.
Note
Содержание 3256
Страница 22: ...3 8 EB 8065 EN...
Страница 44: ...5 18 EB 8065 EN...
Страница 70: ...12 2 EB 8065 EN...
Страница 72: ...13 2 EB 8065 EN...
Страница 74: ...14 2 EB 8065 EN...
Страница 75: ...EB 8065 EN 14 3...
Страница 76: ...14 4 EB 8065 EN...
Страница 80: ...15 4 EB 8065 EN...
Страница 81: ......
Страница 82: ......
Страница 83: ......