Design and principle of oper-
ation

The regulator consists of the Type 2469 Valve
with restriction (orifice), seat and plug, the
closing actuator with operating diaphragm as
well as the thermostat with set point adjuster,
capillary tube and temperature sensor.

The regulator is designed to keep the flow rate
and temperature constant at the adjusted set
point. The valve closes when the controlled
variable increases.

Versions for safety equipment are addition-
ally equipped with a Type 2403 Safety Ther-
mostat to function as safety temperature mon-
itors (FR/TR/STM). They can also be
equipped with a Type 2439 K Safety Thermo-
stat to function as safety temperature limiters
(FR/TR/STL). For further details, refer to the
Mounting and Operating Instructions:
EB 2183 EN

for Type 2403 and

EB 2185 EN

for Type 2439 K.

The medium flows through the valve in the di-
rection indicated by the arrow on the body.
The flow rate is determined by the area re-
leased between the adjustable restriction
(1.2) and the valve plug (3).
The high pressure upstream of the restriction
is transmitted through the attached control
line to the high-pressure side of the actuator.
The low pressure created downstream of the
restriction acts on the low-pressure side of the
operating diaphragm (6.1) through a bore in
the plug.
The differential pressure created by the re-
striction is converted into a positioning force
at the operating diaphragm. This force is used
to move the valve plug depending on the
force of the positioning spring (5).

The medium temperature creates a pressure
in the temperature sensor, which is transmit-
ted through the capillary tube (24) to the op-
erating bellows (23) where is it converted into
a positioning force. This force moves the cou-
pling rod (8) and thus the valve plug (3) de-
pending on the force of the spring (21)
pretensioned by the set point adjuster (22).

The largest signal is used to actuate the valve.

2

Installation

Choose a place of installation where the per-
missible ambient temperature of 80 °C is not
exceeded.

NOTICE

Protect the regulator against frost when it is
used to control freezing process media.

2.1

Mounting position

Install the regulator in a horizontal pipeline
with the actuator and thermostat vertically
suspended (pointing down). Regulators in
DN 15 to 25 can also be installed in vertical
pipelines.
Use the included connection nuts with welding
ends to connect the regulator. Make sure the
direction of flow matches the arrow on the
valve body.

2.1.1 Strainer

Install a strainer (SAMSON Type 1NI) up-
stream of the regulator to prevent that any
sealing parts, weld spatter and other impuri-
ties carried along by the process medium im-
pair the proper functioning of the valve,
above all the tight shut-off.

4

EB 3132-2 EN

Design and principle of operation

Содержание 2469

Страница 1: ...Flow and Temperature Regulator Type 2469 2430 K Mounting and Operating Instructions EB 3132 2 EN Edition November 2011 Fig 1 Type 2469 2430 K...

Страница 2: ...point adjustment 8 3 2 1 Flow rate 8 3 2 2 Temperature 8 4 Maintenance Replacing parts 8 4 1 Cleaning or replacing the plug 9 4 2 Replacing the diaphragm 9 5 Troubleshooting 10 6 Description of the n...

Страница 3: ...conformity that includes information about the applied conformity assessment procedure The declaration of conformity is available on request 4 For appropriate operation make sure that the regulator i...

Страница 4: ...he plug The differential pressure created by the re striction is converted into a positioning force at the operating diaphragm This force is used to move the valve plug depending on the force of the p...

Страница 5: ...ng 1 Valve body 1 1 Connection nut with gasket and welding end 1 2 Restriction orifice plate 2 Seat 3 Plug section with guide nipple 4 Plug stem 5 Positioning spring 6 Actuator 6 1 Operating diaphragm...

Страница 6: ...tire length is immersed in the process medium Choose a place of installation where neither overheating nor considerable idle times oc cur Weld in a sleeve with G or G female thread at the place of ins...

Страница 7: ...10 11 0 01 0 02 0 03 0 05 0 1 0 2 0 3 0 5 1 2 3 4 5 6 7 8 910 15 0 4 KVS 1 2 5 V m3 h DN 15 DN20 KVS6 3 DN25 KVS8 DN32 KVS12 5 DN40 KVS16 203 DN50 KVS20 253 4 Nominal size DN 15 20 25 32 40 2 50 2 KV...

Страница 8: ...ermometer 4 Turn the adjuster clockwise to reduce P the temperature 4 Turn the adjuster counterclockwise Q to increase the temperature The adjusted temperature set point can be lead sealed through the...

Страница 9: ...50 unscrew the stop per and pull out the plug section 5 Thoroughly clean the seat and plug sec tion Check that the control line is not clogged If the plug is damaged replace the entire plug section 4...

Страница 10: ...ential pressure across the plant with the plant drag Min differential pressure differential pressure at restriction V KVS Strainer clogged Drain the strainer s filter and clean it Valve incorrectly in...

Страница 11: ...hermowell with conductive paste remove the thermowell and use a sensor with a smaller time constant Fig 5 Nameplate 1 Model number 2 Modification index 3 Date of manufacture 4 Type designation Entries...

Страница 12: ...led 4 Installation drawing 8 Dimensions in mm and weights Nominal size DN 15 DN 20 DN 25 DN 32 DN 40 DN 50 Pipe d 21 3 26 8 32 7 42 48 60 Connection R G G 1 G 1 G 1 G 2 G 2 Width across flats SW 30 36...

Страница 13: ...d R G G G G 185 220 185 220 12 19 9 5 16 Fig 6 Dimensional drawings Connection nuts with threaded ends Connection nuts with flanges Flanged body DN 32 40 and 50 Connection nuts with welding ends Valu...

Страница 14: ...14 EB 3132 2 EN...

Страница 15: ...EB 3132 2 EN 15...

Страница 16: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de EB 3132 2 EN S Z 2011 12...

Отзывы: