EB 2540 EN
3-5
Design and principle of operation
Table 3-1:
Technical data for main valve · All pressures in bar (gauge)
Type 2406 as main valve, balanced by a diaphragm
Valve size
NPS 2½
DN 65
NPS 3
DN 80
NPS 4
DN 100
–
DN 125
NPS 6
DN 150
Pressure rating
Class 125, 150, 300
·
PN 16, 40
C
V
coefficients
K
VS
coefficients
60
50
94
80
145
125
–
250
450
380
Actuator area
50 in² · 320 cm²
Leakage class according to ANSI/
FCI 70-2 or IEC 60534-4
Soft-seated, minimum Class IV
Permissible differential pressure Δp
175 psi · 12 bar
Perm. temperature
–5 to +195 °F · –20 to +90 °C
1)
Conformity
·
Type 2422 as main valve, balanced by a diaphragm, with Type 2420 Actuator
Valve size
NPS 8
DN 200
NPS 10
DN 250
NPS 12
DN 300
NPS 16
DN 400
Pressure rating
Class 125, 150, 300
2)
·
PN 16, 40
C
V
coefficients
K
VS
coefficients
760
650
930
800
1440
1250
2400
2000
Actuator area of Type 2420
320 cm²
640 cm²
Leakage class according to ANSI/
FCI 70-2 or IEC 60534-4
Soft-seated, minimum Class IV
Permissible differential pressure Δp
145 psi · 10 bar
90 psi · 6 bar
Perm. temperature
–5 to +195 °F · –20 to +90 °C
1)
Conformity
·
1)
Max. 175 °F (80 °C) for EPDM and NBR versions
2)
NPS 12 and 16: Class 150/PN 16 only
Содержание 2404-2
Страница 12: ...1 8 EB 2540 EN Safety instructions and measures...
Страница 18: ...2 6 EB 2540 EN Markings on the device...
Страница 34: ...3 16 EB 2540 EN Design and principle of operation...
Страница 60: ...11 2 EB 2540 EN...
Страница 62: ...12 2 EB 2540 EN...
Страница 64: ...13 2 EB 2540 EN...
Страница 72: ...14 8 EB 2540 EN...
Страница 75: ......