troubleshooting Guide

Issue:

 no AC output - Green LeD is not on, Yellow LeD is on, Buzzer is on  

PoSSIBLe CAUSeS: 
Low DC input voltage shut down due to DC input voltage at the inverter terminals dropping 
below 10.0 VDC. Auto reset when the DC input voltage is > 11.5 VDC.

SUGGeSteD ReMeDIeS:
• 

Low battery terminal voltage. recharge the battery. If  battery voltage does not rise to fully 
charged voltage even after long charging time, replace the battery. 

• 

Excessive drop in DC input wires due to thin DC input wires. Check firmness of connections and 
increase wire size

• 

If the battery terminals read higher voltage at no load but the terminal voltage drops ap-
preciably when the load is turned on, the battery may have sulfated due to undercharging. 
Equalize the battery (only flooded or wet cell types).

Issue:

 no AC output - Green LeD is not on, Yellow LeD is on, Buzzer is oFF

PoSSIBLe CAUSeS: 
1. 

over temperature shutdown

2. 

High DC input voltage shut down. DC input voltage is > 15.5 V. Auto-reset when voltage  
< 15.5 VDC

SUGGeSteD ReMeDIeS:
IF Cause #1:
• 

fan failure: Check that the fan runs when the unit is loaded to > 8 to 12 W

• 

Ventilation openings are blocked: remove any obstructions in the ventilation openings 

• 

Not enough cool, replacement  air: Install the unit in an open, cool and dry area

• 

High ambient temperature > 40 C: The temperature of the unit will slowly rise even if the 
fan is working

IF Cause #2:
• 

The battery charger may be charging at > 15.5 V, especially during Equalization. Disconnect 
the DC input of the inverter when equalizing the batteries > 15.5 VDC

• 

It is likely that 24 VDC battery has been connected instead of 12 VDC battery. oNLY USE A 
NoMINAL 12 VDC bATTErY WITH THIS ProDUCT.

Issue:

 no AC output - Green, Red and Yellow LeDs are not on and Buzzer is oFF

PoSSIBLe CAUSe: No DC input power.

SUGGeSteD ReMeDIeS:
• 

Check DC voltage at the DC input terminals

• 

If DC input cable with cigar plug is being used, the 8 A fuse in the front of the cigar plug may 
have blown if the load being powered was > 80 W. replace the fuse in the cigar plug, if blown. 

• 

If powered from the cigar receptacle in a vehicle, the fuse in the vehicle that is supplying 
the cigar receptacle may have blown. Check and replace. After replacing the fuse, check DC 
input voltage at the inverter terminals. If DC input voltage is available, the internal fuses may 
have blown. Call Technical Support.

• 

If DC input cable with battery clamps is being used without inline fuse, the internal DC fuses 
in the inverter may have blown. Call technical support

• 

If DC input cable with battery clamps is being used with inline fuse, check the inline fuse and 
replace if blown. If the fuse is intact, the internal DC fuses in the inverter may have blown. 
Call technical support.

Содержание SAM-450-12E

Страница 1: ...DC AC Inverter Model SAM 450 12E Please read this manual before installing your inverter Owner s Manual ...

Страница 2: ...ction 5 Section 4 How Your Inverter Works 6 Section 5 Installation DC Input Power Source Grounding Mounting 7 SECTION 6 Input Output Connections Operation 8 Section 7 Protective Features of the Inverter 10 Section 8 Common Problems 11 Section 9 Trouble Shooting Guide 12 Section 10 Specifications 14 Section 11 Warranty 15 ...

Страница 3: ...cludes 12 VDC cigarette plug connections and terminal connections 4 This is not a toy keep away from children 5 DO NOT insert objects into air vents CAUTIONS 1 Do not use with positive ground electrical systems the majority of modern automobiles RVs trucks and boats are negative ground Reverse polarity connection will result in a blown fuse and may cause permanent damage to the inverter 2 This inv...

Страница 4: ...el 7 Red Thumb Screw M4 size for Positive battery input terminal 8 Black Thumb Screw M4 size for Negative battery input terminal NOTE The Negative terminal is internally bonded to the metal chassis of the inverter 9 Opening for cooling fan discharge Accessories 10 Battery input cable set with battery clamps 11 Battery input cable set with cigar plug Front Panel 2 3 4 5 6 1A 1B 1C Back Panel 7 8 9 ...

Страница 5: ...introduction of L I T signal interference may occur on TV pictures audio system or radio equipments Now you can enjoy a clean and powerful AC source Soft Start Circuit Provides three major features First gradual voltage ramp up during inverter start up This eliminates failed cold starts under load Second output that momen tarily dips in voltage and quickly recovers This eliminates most shutdowns f...

Страница 6: ... waveform that has charac teristics similar to the sine wave shape of utility power This type of waveform is suitable for most AC loads including lin ear and switching power supplies used in electronic equipment transformers and motors See Fig 1 below The modified sine wave produced by the inverter has an RMS root mean square voltage of 230 volts which is the same as standard household power Most ...

Страница 7: ... bonded connected to the Negative DC input terminal 8 When the unit is operated in a Negative Grounded Vehicle System the Negative of the vehicle bat tery is bonded to the metal chassis of the vehicle the metal chassis of the inverter will be automatically bonded to the Vehi cle Chassis Ground WARNINGS If the inverter is not being used in a vehi cle please ensure that the Negative of the battery i...

Страница 8: ... sure you have not reversed the polarity Reverse polarity connection will result in a blown fuse and may cause permanent damage to the inverter OPERATING ENVIRONMENT The inverter should only be used in loca tions that meet the following criteria DRY Do not allow water or other liquids to come into contact with the power inverter In marine applications do not install the inverter below or near the ...

Страница 9: ...ched on This may prematurely trigger the overload protection When a load is switched on it may require initial higher power surge to start If multiple loads are being powered they should be switched on one by one so that the inverter is not overloaded by the higher starting surge OPERATION Plug the cord from the equipment you wish to operate into the AC receptacle The green LED indicator lights to...

Страница 10: ...een LED Power 4 OFF Yellow LED Input Fault 5 ON Buzzer OFF Reset Auto reset When DC input voltage 15 5 V OVERLOAD PROTECTION The inverter will automatically shut down when the continuous draw exceeds rated watts Red LED FAULT 3 ON Green LED Power 4 ON Yellow LED Input Fault 5 OFF Buzzer OFF Reset Manual reset Switch OFF wait for around 3 min switch ON SHORT CIRCUIT PROTECTION The inverter will shu...

Страница 11: ... each pow er tool carefully to accurately determine the tool s input wattage Please remember that the power needed to start the power tool may be as much as 2 to 6 times its continuous wattage requirements BUZZING SOUND IN AUDIO SYSTEMS Some inexpensive stereo systems and boom boxes emit a buzzing sound from their speakers when operated from the power inverter This occurs because the power supply ...

Страница 12: ...unit in an open cool and dry area High ambient temperature 40 C The temperature of the unit will slowly rise even if the fan is working IF Cause 2 The battery charger may be charging at 15 5 V especially during Equalization Disconnect the DC input of the inverter when equalizing the batteries 15 5 VDC It is likely that 24 VDC battery has been connected instead of 12 VDC battery ONLY USE A NOMINAL ...

Страница 13: ...SE Low DC input voltage alarm due to DC input voltage 10 5 VDC Will automati cally reset when 10 5 VDC SUGGESTED REMEDIES Low battery terminal voltage Recharge the battery If battery voltage does not rise to fully charged voltage even after long charging time Replace the battery Excessive drop in DC input wires due to thin DC input wires Check firmness of connections and increase wire size If the ...

Страница 14: ...5 VDC Low Input Voltage Shutdown 10 0 VDC Auto reset at 11 5 VDC High Input Voltage Shutdown 15 5 VDC Auto reset at 15 5 VDC Overload And Leakage Shut Down Latches in shutdown condition Manual reset by switching off the ON OFF switch waiting for 3 minutes and switching on the On Off switch Cooling Load controlled fan Comes on at 8 to 12W Over Temperature Shutdown By sensing internal hot spot Auto ...

Страница 15: ... a reasonable number of op portunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh water spray or wate...