The output voltage of the paralleled modules or the common DC bus (before the Schottky Di-
odes 

D1

) can be adjusted between 13.8 V and 14.6 V by adjusting the voltage of each module 

individually as per the following procedure ( This procedure is explained for SEC-100BRM 
which has 5 modules ). 

The voltage at the output terminals LOAD + and LOAD –   will be as 

follows : 
 
At no external load  

Module voltage minus 0.2V 

At 10A load 

 

Module voltage minus 0.4V 

At loads > 10A 

Module voltage minus 0.4V minus 5mV per Amp above 10A  

 

Procedure 
 

• 

Switch off the unit and unplug the power cord. 

• 

The output voltage of each individual power supply module (

PSM

) is adjusted one by one 

starting  from the left most module – PSM 1 and progressing to the right most module – 
PSM No. 5 ( for SEC-100BRM-220 ). 

AC input is connected only to the module being 

adjusted. AC input to the remaining modules is disconnected 

• 

Remove the AC input connections ( female quick connect terminals connected to the L and 
N male tab terminals on the modules – Fig. 1 ) from PSM Nos. 2, 3, 4 and 5. Temporarily 
insulate these female quick connect terminals with insulating tape for safety. 

Now, only 

PSM No. 1 can be energized. 

• 

Switch on the power supply. 

Only PSM No. 1 will operate

. Adjust the output voltage of  

this module to the desired value with the help of potentiometer 

VR1

 (Fig.1) Measure the 

voltage at the screw terminals 

S5

 and 

S6

 (Fig.1) 

• 

Switch off the power supply. Remove the AC input connection from PSM No. 1. Temporar-
ily insulate these terminals with insulation tape. Remove temporary insulation from the AC 
connectors for PSM 2 and connect them to PSM 2. 

Now only PSM 2 can energize.  

• 

Switch on the power supply. 

Only PSM No. 2 will operate

. Adjust the output voltage of  

this module to the desired value with the help of potentiometer 

VR1

 (Fig.1). Measure the 

voltage at the screw terminals 

S5

 and 

S6

 (Fig.1) 

• 

Continue to adjust the voltage of the remaining Module Nos. 3, 4 and 5 individually as 
explained above making sure that 

the AC power is connected to only the module being 

adjusted. 

• 

After all the modules have been adjusted to the same output voltage, connect the AC input 
back to all the five modules.  

• 

Power on the unit and check that all the 5 “

PSM Status”

 LEDs are lighted. This will con-

firm that the voltage adjustment has been completed successfully. 

 

NOTE: As explained under Design & Principle of Operation on page 3, it is likely that the 
minimum internal preload current for the new value of the output voltage may not be 
sufficient to provide adequate feedback signal strength resulting in shut down of one or 
more PSM(s) when no external load is present (The associated PSM Status LED will flash 
and also, the associated signal for remote indication will oscillate between High and 
Low). In such a case, apply an external load to increase the feed back signal strength. If 
there is no other defect, the PSM(s) that were shut down will also operate normally.  
 
INSTALLATION AND REMOVAL OF POWER SUPPLY MODULES 
 
NOTE: 

INSTALLATION AND REMOVAL OF POWER SUPPLY MODULES 

 

SHOULD BE PERFORMED ONLY BY QUALIFIED PERSONNEL 

 
CAUTION! 

Before removing a defective module or installing a new one, switch off the 230 V , 50/60 Hz 
input power and unplug the power cord from the mains outlet. 
 

NOTE: 

Please refer to the layout diagram of the module at Figure. 1 located on page 17

Содержание SEC-40BRM-220

Страница 1: ...0BRM 220 SEC 80BRM 220 SEC 100BRM 220 Please read this manual before operating your power supply INSTALLATION OPERATING MANUAL EXPANDABLE DC POWER SUPPLY 230V AC INPUT N 1 DC Power System with Battery...

Страница 2: ...RIES FOR BACKUP EXPAND OUTPUT POWER BY ADDING POWER MODULES UP TO 100 AMPS CONTINUOUS POWER VOLT AMPERE METER OPERATION STATUS L E D FAN FAILURE ALARM AND WARNING L E D REMOTE MONITORING AND INDICATIO...

Страница 3: ...re 3 Front panel controls and indicators 4 Rear panel controls 4 5 Protections 5 Installation and operation 6 Operation of battery back up 7 Output voltage adjustment 8 9 Installation and removal of m...

Страница 4: ...2 POLE 2 WIRE RECEPTACLE THAT HAS NO GROUNDING REPLACEMENT OF POWER CORD PLUG THE POWER CORD IS PROVIDED WITH A MOULDED STANDARD EUROPEAN 2 POLE 3 WIRE GROUNDING PLUG SCHUKO 250V 16A THE PLUG MAY BE R...

Страница 5: ...ELOW TO CONNECT ANY DEVICE TO THE POWER SUPPLY THESE CABLE SIZES ARE VALID WHEN THE DEVICE IS WITHIN 6 FT DIS TANCE FROM THE POWER SUPPLY THICKER WIRING WILL BE REQUIRED FOR LONGER DISTANCES THINNER W...

Страница 6: ...PSM is required to be interconnected with one another to a common SHARE BUS through a pair of parallel pins marked JUMP 1 and jumper wires Fig 1 and 2 For proper operation of the current share control...

Страница 7: ...CH The rocker switch will illuminate when switched on 1B BREAKER A circuit breaker provides protection on the input side against overload 2 VOLTMETER AMMETER A combined voltmeter and ammeter are provi...

Страница 8: ...omatically once the short circuit condition is removed CURRENT LIMITING The unit will enter this mode when the load tries to draw more than the limiting values of currents as shown in the specificatio...

Страница 9: ...n the unit by pressing the power on off switch to on position The switch will be illuminated confirming that input power is available 8 A short beep may be generated by the temperature fault alarm cir...

Страница 10: ...D will be as follows At no external load Approx 14V At 10 A load Approx 13 8V At loads 10A Approx 13 8V minus 5mV per Amp above 10A THE BATTERY SHOULD BE LOCATED IN A WELL VEN TILATED AREA TO SAFELY D...

Страница 11: ...utput voltage of the module The adjustment range is 13 8 V to 14 6 V For the forced current share control to work properly it is important that the output voltage of each module connected in parallel...

Страница 12: ...C connectors for PSM 2 and connect them to PSM 2 Now only PSM 2 can energize Switch on the power supply Only PSM No 2 will operate Adjust the output voltage of this module to the desired value with th...

Страница 13: ...ector Connection to the opto coupler PCB and on ward to the D Sub connector for remote indication is made using color coded pair of wires for each of the 5 modules Please see the colour code for PSM 1...

Страница 14: ...RE THAT THERE IS NO BREAK IN THE SHARE BUS DAISY CHAIN AND THAT ALL THE JUMP1 TERMINALS ARE INTERCONNECTED 6 The module can now be removed TROUBLE SHOOTING POWER ON OFF SWITCH DOES NOT LIGHT WHEN SWIT...

Страница 15: ...n LED would extinguish or flash Reduce the load drawn to a value less than the combined maximum rated output of the working modules If the voltage does not rise to the rated voltage of 13 65 V to 13 3...

Страница 16: ...io Filters are used to limit the noise to acceptable level 3 Switching power supplies are also recipients of radio interference The nor mal operation of the power supply can be disturbed due to RF noi...

Страница 17: ...outlet circuits receptacles In such cases disconnect devices connected to the other AC outlet circuits receptacles served by this GFCI 6 Following additional guidelines may be followed to reduce the...

Страница 18: ...the earth ground through the earth ground pin of the AC power outlet receptacle Avoid connecting referencing the DC negative output terminal of the power supply to the earth ground e Connect a 1 4 wav...

Страница 19: ...T LIMIT 48A 72A 96A 120A OUTPUT RIPPLE PEAK TO PEAK 150mV OUTPUT NOISE PEAK TO PEAK 1V 0 9V 0 8V 0 7V COOLING FORCED AIR 2 FANS OPERATING TEMPERATURE 0 TO 40 C PROTECTIONS SHORT CIRCUIT YES CURRENT LI...

Страница 20: ...e and Negative output BUS Bars L N L line and N neutral terminals for 120V 60 Hz input power supply wires LED 1 Terminal for ON status for opto isolated remote indication LED 2 Terminal for LED PSM st...

Страница 21: ...socket for the missing sandwiched module s should be shorted by inserting a shorting link to pre vent a break in the daisy chain Fig 3 Jump 1 Jump 1 Jump 1 Jump 1 Jump 1 1 Female socket terminal of t...

Страница 22: ...y the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or h...

Страница 23: ...Attach copy of receipt here for your records Date purchased Additional notes Purchased from 20...

Страница 24: ...Thank you for purchasing a Samlex power supply product Samlex America Inc 110 17 Fawcett Road Coquitlam B C V3K 6V2 Canada SEC 40 60 80 100BRM _230_Feb2008...

Отзывы: