PREPARING THE CHARGER FOR OPERATION

Selecting AC input voltage

The charger is

pre-set to operate from input AC voltage of 120 VAC, 60 Hz

.

To operate the charger from AC input voltage of 230 VAC, 50 Hz, change the internal
setting as follows :

1. Remove the 4 screws on the ammeter side of the top cover
2. Gently slide the top cover out by 2 to 3 inches. (

Caution !

The top cover will be

restrained from fully sliding out by the wires connecting the ammeter, LED and
the fan )

3. Locate the jumper wire with a quick female disconnect. In the pre-set condition,

it is connected to the male vertical pin marked “115 V”. Pull this female discon-
nect upwards to disconnect from the “115 V” position. Connect this to the male
vertical pin marked “230 V”

4. Replace the fuse with the fuse recommended for 230 VAC operation ( See fuse

rating at page 12)

5. Replace the AC plug of the power cord with a suitable 3 pin grounded plug to

mate with the 230 VAC outlet. (

Caution !! The new plug should have 3 poles

i.e. Line ( L ) , Neutral ( N ) and Earth ground. Color code for the power
cord conductors is : Line ( L ) - Black , Neutral ( N ) – White and Earth
ground – Green )

Selecting the Type of Battery and Charging Stages

The Float Voltage and Boost Voltage (Also called Absorption or Overcharge Voltage ) of
different types of Lead Acid Batteries are different. Also, when a charger is used to charge
a battery and simultaneously supply a load , the Boost Stage is required to be disabled to
prevent overcharging of the battery . A

Dip Switch

is provided on top of the output

terminals for selecting the battery type and for disabling the Boost Stage when charging
loaded batteries. The following selections can be made with the help of the Dip Switch.

CAUTION ! (Do not change the Dip Switch setting when the charger is operating.
Always change the Dip Switch setting when the charger is off , i.e. after disconnect-
ing the charger from the AC input power )

NOTE : The voltages are for a temperature of 80 Degrees F

DIP SWITCH SETTINGS - SEC-1215A / SEC-1230A

S1

S2

Float

Boost

Battery Type

Charging Stages

OFF *

ON *

13.5 V * 14.4 V *

Flooded / AGM *

3 Stages (Stages 1, 2, 3)

ON

OFF

13.5 V

14.0 V

Gel Cell

3 Stages (Stages 1,2,3)

OFF

OFF

13.5 V

Disabled

Battery with load

2 Stages (Stages 1, 3)

ON

ON

Caution !!! Do not use this setting

* Factory pre set in this position

Page 7

Содержание SEC - 1215A

Страница 1: ...Owner s Manual Please read this manual before operating your charger Switch Mode Automatic Lead Acid Battery Charger Model SEC 1215A SEC 1230A SEC 2415A...

Страница 2: ...IMPORTANT SAFETY PRECAUTIONS 2 DESCRIPTION AND FEATURES 3 CHARGING STAGES 4 PROTECTIONS 5 INSTALLATION 6 CHARGER OPERATION 7 8 9 10 TROUBLESHOOTING 11 12 INTERNAL FUSE RATINGS 12 SPECIFICATIONS 13 WAR...

Страница 3: ...n the same compartment as batteries Charger Related Do not operate the charger in a closed in area or restrict ventilation in any way Install in a well ventilated cool dry place The charger must not b...

Страница 4: ...simultaneously without use of an external battery isolator Monitoring through ON status LED and Ammeter Temperature controlled cooling fan SEC 1230A SEC 2415A Protections against short circuit over c...

Страница 5: ...e threshold of battery gassing termed boost or absorption voltage the charger automatically switches over to Stage 2 Boost or Absorption Stage The value of this voltage depends upon the type of batter...

Страница 6: ...draw a higher current than these limits the output voltage of the unit will start to drop The unit will automatically recover when the overload condition is removed Reverse Battery Connection Cut Off...

Страница 7: ...EC 1230A 0 19 inches CAUTION For firm connection when using stranded cable crimp solder pin style terminal on the charger end of the DC cables used for connecting to the battery other DC loads Cables...

Страница 8: ...cord conductors is Line L Black Neutral N White and Earth ground Green Selecting the Type of Battery and Charging Stages The Float Voltage and Boost Voltage Also called Absorption or Overcharge Voltag...

Страница 9: ...he charger In case the AC power fails or if there is no output from the charger the isolating diodes will prevent charging discharging among the batteries connected to the banks CAUTION When a bank co...

Страница 10: ...rame or engine block which is away from battery Do not connect to carburetor fuel lines or sheet metal body parts 6 For a positive grounded vehicle connect the negative black DC cable from the charger...

Страница 11: ...ent drawn by the DC load is below the maximum current rating of the charger Switch on the charger and then the DC load In a DC UPS Un interruptible Power Supply the charger simultaneously powers the D...

Страница 12: ...e charger is also feeding other DC load s in parallel with the battery The Dip Switch is not selected for Battery with Load Change Dip Switch setting to Battery under Load see under Powering other DC...

Страница 13: ...s Ensure that the starting inrush current or the maximum operating current of the load is lower than the current limit value of the charger INTERNAL FUSE RATINGS Both the AC side and DC sides have fus...

Страница 14: ...82 Short Circuit Overload 3 120 VAC 60Hz 230 VAC 50 Hz 50 60 Hz 14 VDC or 14 4VDC or Disabled 13 5 VDC 30A 0 40o C 2 9kg 6 4 lbs 10 8 x 8 4 x 3 3 273 x 214 x 82 Short Circuit Overload Over temperatur...

Страница 15: ...s the Warrantor is unable to remedy the defect after having a reasonable number of opportunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by...

Страница 16: ...110 17 Fawcett Rd Coquitlam B C Canada V3K 6V2 T 604 525 3836 F 604 525 5221 e mail samlex samlexamerica com website www samlexamerica com 4 4 4 4XJUDI BOVBM...

Страница 17: ...Samlex America Inc 110 17 Fawcett Road Coquitlam B C Canada V3K 6V2 e mail samlex samlexamerica com website www samlexamerica com SEC1215A 1230A 2415A 031004...

Отзывы: