background image

3

WIRING DIAGRAM

1.  INPUT (+)
2.  INPUT (-)
3.  LOAD (-)
4.  LOAD (+)
5.  STOP (+)
6.  PROG/SWITCH (-)

OPERATION

The PDS switches the LOAD output if it detects motion or if the PROG/SWITCH input 
is briefly (<1 sec) connected to the negative (–) pole of the battery. The LOAD will 
be switched off with a delay once the PDS no longer detects motion and the PROG/
SWITCH input is no longer connected to the negative (–) pole of the battery.  
The user can set the duration of the delay from 10 seconds up to 30 minutes.

Overvoltage

If the input voltage exceeds 16 V (32 V for 24 V systems) for longer than 1 second, 
the PDS will switch off. The PDS will resume normal operation once the voltage drops 
below 15.8 V for longer than 5 seconds.

Undervoltage

If the input voltage drops below 10.5 V (21 V for 24 V systems) for longer than  
5 seconds, the PDS will switch off. The PDS will resume normal operation once the 
voltage exceeds 12.6 V for longer than 5 seconds.

STOP input

The above will only work as described if the STOP input is not connected to the  
positive (+) terminal of the battery. If the STOP input is connected, the PDS  
will not switch on.

Отзывы: