4
PROGRAMMING
The PDS’ switch-off delay duration can be programmed by connecting the PROG/
SWITCH to the negative (-) pole of the battery. Once the connection has been
established for ±15 seconds, the LED and the PDS output will flash once.
The connection must then be broken.
This same connection must briefly be made again to select the correct configuration
– the LED will light up as feedback (the output will also be briefly activated).
Configuration #1 has then been selected. Making the connection again will select
configuration #2, etc.
If no connection has been made for ±4 seconds, the LED (and the output) will
indicate the selected configuration again. Example: Configuration #4 has been
selected, the LED will flash 4 times.
CONFIGURATION TABLE
#
Switch-off delay
1
10 seconds
2*
1 minute
3
3 minutes
4
6 minutes
5
15 minutes
6
30 minutes
*) Default setting
ELECTRICAL DETAILS
Description
12 V
24 V
Auto 12 V / 24 V detection
Output current (continuous)
10 A
Output current (peak)
± 70 A (max. 170 µs) @ 12 V
Overload protection (shutdown)
± 14 A (after 5 sec)
Power consumption (standby)
± 2 mA
Undervoltage switch-off threshold
Start-up voltage after undervoltage switch-off
10.5 V
12.6 V
21.0 V
25.2 V
Overvoltage switch-off threshold
Start-up voltage after overvoltage switch-off
16.0 V
15.8 V
32.0 V
31.6 V