PROGRAMMING

The PDS’ switch-off delay duration can be programmed by connecting the PROG/
SWITCH to the negative (-) pole of the battery. Once the connection has been 
established for ±15 seconds, the LED and the PDS output will flash once.  
The connection must then be broken.
This same connection must briefly be made again to select the correct configuration 
– the LED will light up as feedback (the output will also be briefly activated). 
Configuration #1 has then been selected. Making the connection again will select 
configuration #2, etc.
If no connection has been made for ±4 seconds, the LED (and the output) will 
indicate the selected configuration again. Example: Configuration #4 has been 
selected, the LED will flash 4 times.

CONFIGURATION TABLE

#

Switch-off delay

1

10 seconds

2*

1 minute

3

3 minutes

4

6 minutes

5

15 minutes

6

30 minutes

  

*) Default setting 

ELECTRICAL DETAILS

Description

12 V

24 V

Auto 12 V / 24 V detection

Output current (continuous)

10 A

Output current (peak)

± 70 A (max. 170 µs) @ 12 V

Overload protection (shutdown)

± 14 A (after 5 sec)

Power consumption (standby)

± 2 mA

Undervoltage switch-off threshold

  

  Start-up voltage after undervoltage switch-off

10.5 V

12.6 V

21.0 V

25.2 V

Overvoltage switch-off threshold

  

  Start-up voltage after overvoltage switch-off

16.0 V

15.8 V

32.0 V

31.6 V