background image

3

 

 

Warning!

When the surface of the solar panel / array is exposed to sunlight, a DC voltage appears at the 
output terminals turning it into a live voltage source. For example, a 24 V nominal solar panel my 
put out an open circuit voltage of around 45 VDC that may produce electrical shock. Multiple so-
lar panels connected in series (to increase the output voltage) will put out higher lethal voltages  
To avoid any electrical shock hazard during installation, make sure that the solar panel / array is 
covered with an opaque (dark) material to block solar irradiation.

 

INSTALLATION

Installation procedure (See Fig. 1 and Fig. 2) 

The MC4 connectors provided are compatible for use with AWG #10 or AWG #12 wire with outer insulation 
diameter 3 – 6 mm.  Wires may be single conductor, Type UF (Underground Feeder - marked as sunlight 
resistant), Type SE (Service Entrance) or Type USE/USE-2 (Underground Service Entrance).

1.  Strip 1/4” of the wire insulation using a wire stripper. Take care not to cut individual strands.

2.  Insert the bare conductor into the crimping area (4 of Fig. 1) of the metallic mating contact and crimp 

using a special purpose crimping tool. The end may be soldered if the crimping tool is not available. 
Take care that the solder does not fl ow beyond the crimp area.

3.  Insert the metallic mating contact with the crimped wire through the cable gland into the insulated 

housing, till the metallic pin fi ts snug into the housing.

4.  Tighten nut (3 of Fig.1) so that the rubber bush is compressed around the wire entry to ensure proper 

sealing.

Содержание MC4-2

Страница 1: ...f MC4 Connectors See Fig 1 The connectors can be crimped soldered to wire size AWG 10 or AWG 12 with an outer insulation diameter of 3 to 6 mm 1 Outer insulated housing 2A Tin plated Copper female mating contact 2B Tin plated Copper male mating contact 3 Nut with internal rubber bush for tightening the sealing around the wire entry 4 Crimping area 1 2A 6 3 2B 4 MC4 Female Connector PV KBT4 6I MC4 ...

Страница 2: ...s attempted 1 3 3 1 2 2 Fig 2 Snap in Locking System Wire Connections on Solar Panels See Fig 3 Most solar panels come with approximately 3 ft of Positive and Negative wire One end of each wire is connected to the junction box of the panel In most solar panels for example solar panels manufactured by Samlex Solar the other end of each wire is terminated with an MC4 connector The Positive wire has ...

Страница 3: ... use with AWG 10 or AWG 12 wire with outer insulation diameter 3 6 mm Wires may be single conductor Type UF Underground Feeder marked as sunlight resistant Type SE Service Entrance or Type USE USE 2 Underground Service Entrance 1 Strip 1 4 of the wire insulation using a wire stripper Take care not to cut individual strands 2 Insert the bare conductor into the crimping area 4 of Fig 1 of the metall...

Страница 4: ...ing a reasonable number of opportunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh water spray or wa...

Отзывы: