21
9
Using the Charger
ENG
9.1.1 I phase (bulk)
The "STATUS" LED constantly lights Red.
In the first stage of the charging process, the depleted battery is charged with a constant
current until the battery voltage reaches I phase setting voltage (13.5V/27.0V or 13.8V/27.6V).
When the battery reaches this voltage level, the charging current gradually drops.
When the current drops down to 80%, the charger switches over to Uo phase setting voltage
(14.0V/28.0V or 14.4V/28.8V or 14.8V/29.6V). Typically the battery is charged to 70-80% of its
capacity.
9.1.2 Uo phase (absorption)
The "STATUS" LED constantly lights Orange.
This main charging phase could be set to the maximum of 4/6/8 hours or unlimited, and the
current rises again to its maximum value. The current remains constant as long as the battery
voltage is below Uo phase setting voltage (14.0V/28.0V or 14.4V/28.8V or 14.8V/29.6V).
After reaching the setting voltage, it remains constant. However, the current drops again.
Within this main charging phase, the battery is charged to 95% of its capacity.
Note
The charging voltage and the period for the main charging phase (Uo phase) can be selected using
the switch field S1.
9.1.3 U phase (float)
The "STATUS" LED constantly lights Green. If the current decreases to 10% or under the
rated current or if the time limit of 4/6/8 hours is exceeded, then the charger switches over to
economy charging (13.5V/27.0V or 13.8V/27.6V).
Note
Batteries may be charged separately from each other if the chargers have double charging or three-
fold charging connections. The outputs are separated internally by diodes, thus the weaker battery will be
always first charged to the charging level of the stronger battery.
Attention
The maximum battery capacity should NOT exceed the specified capacity, otherwise the
functions of the individual charging phases could be influenced.
9.1.4 8-day conditioning
If the battery charger stays at U phase for 8 days, it will switch back to 3-stage charging IUoU,
and stay at Uo phase for 60 minutes to revive the battery.
Note
1. 8-day conditioning will be terminated whenever equalization function or half power mode is activated.
2. When the charger is in the equalization stage or half power mode, 8-day conditioning will NOT be
triggered.
Содержание WSC-1230
Страница 3: ...3 Figure 4 WSC 1215 WSC 2408 Charger Top View mm Figure 3 Charger Rear View...
Страница 4: ...4 Figure 6 WSC 1230 WSC 2415 Charger Top View mm Figure 5 WSC 1215 WSC 2408 Charger Side View mm...
Страница 5: ...5 Figure 8 Making Connections Figure 7 WSC 1230 WSC 2415 Charger Side View mm...
Страница 6: ...6 Figure 9 Cable Setup Figure 10 Fork...
Страница 7: ...7 Figure 12 Temperature Sensor TF 100 Figure 11 Switch...
Страница 8: ...8 Figure 14 Remote Controller RC 600 Dimension mm Figure 13 Remote Controller RC 600...
Страница 9: ...9 Figure 16 Remote Controller RC 601D Dimension mm Figure 15 Remote Controller RC 601D...
Страница 10: ...10 Figure 18 Temperature Sensor Setup Figure 17 Making Connections RC 601D...
Страница 31: ...www samlex com www samlex solar com...