WARNING
ENGLISH
Safety precautions
a
This equipment is designed for trained personnel only, who must know the
refrigeration fundamentals, cooling systems, refrigerants and possible damage
that pressurized equipment may cause.
b
Carefully read the instructions contained in this manual; strict observance of
the procedures described is fundamental to the operator’s safety, the perfect
state of the unit and constant performances as declared.
c
Before performing any operation, make sure that the hoses used for
connections have been previously evacuated and that they do not contain
non-condensable gases .
d
Avoid skin contact; the low boiling temperature of the refrigerant (about -30°C)
can cause freezing .
e
Avoid breathing refrigerant vapours.
f
It is recommended to wear suitable protections like safety glasses and gloves;
contact with refrigerant may cause blindness and other personal injuries.
g
Do not operate near open flames and hot surfaces; the high temperatures
decompose the refrigerant releasing toxic and caustic substances which are
hazardous for the operator and the environment.
h
Remove the battery in case of long periods of non-use.
i
Do not keep a low battery inside the instrument
j
Operate the unit only in locations with suitable ventilation and a high number
of air changes.
k
Before disconnecting the instrument from the system, recover the refrigerant
inside the system in order to avoid wasting it in the environment .
l
During operations avoid release of refrigerant to the environment; this
precaution is required by international environmental standards and is essential
to avoid difficult leak detection in a refrigerant polluted environment.
m
Protect the unit from dripping.
n
Do not modify the calibration of safety valves and control systems.
o
If you recover refrigerant from a cooling system equipped with a water
evaporator and/or condenser, it is necessary to drain water from the evaporator
and/or condenser or to keep the circulation pump running during the entire
recovery operation in order to avoid frosting.
FOX - user and service manual
4
Содержание Fox
Страница 2: ......
Страница 3: ...Grupo manom trico digital Manual de uso ESPA OL...
Страница 15: ...Gruppo manometrico digitale Manuale d uso ITALIANO...
Страница 27: ...Digital manifold User s manual ENGLISH...
Страница 39: ...Digitale Monteurhilfe Bedienungsanleitungen DEUTSCH...
Страница 51: ...Manifold digital Manuel d utilisation FRAN AIS...
Страница 63: ......
Страница 64: ......