20 

 

 

SERVICE MENU 

Entrance to the service menu:  
Password 

 [0000] 

 OK 

 

Services settings 

range 

fact. 

Heating circuit 

 

 

Heat source 

 

 

Protection 

 

 

Room thermostat 

Yes/No 

No 

Temperature correction: 

 

T1 Circuit sensor 

 

T2 External sensor 

 

T3 Return sensor 

 

T4 Boiler sensor 

 

-4..+4

ºC 

-4..+4

ºC 

-4..+4

ºC 

-4..+4

ºC 

 




External sensor 

Off/On 

On 

Manual control 

 

 

Screed drying: 

 

Active  

 

Program selection: P1-P7 

 

Yes/No 

P1..P7 

 

No 
P1 

Restore defaults settings 

Yes/No 

No 

 

Heating circuit 

range 

fact. 

Support 

Off/On 

On 

Kind of the system: 

 

Radiators system  

 

Underfloor heating 

 

Und. 

Control method: 

 

Weather control 

 

Continous control 

 

Weat. 

Weather control *: 

 

Heating curve 

 

Curve parallel move 

 
 

-15..15K 

 
 

Preset temperature 

20..40ºC 

35 

Decrease of work mode 

0..15K 

10 

Decrease of thermostat * 

0..30K 

10 

OFF by thermostat* 

Yes/No 

Yes 

Start pump temp. 

10..70ºC 

35 

Min. temperature 

5..40ºC 

20 

Max. temperature 

20..50ºC 

40 

Valve full opening time 

60..200s 

140 

Valve input dead zone 

0.0..2.0K 

1.0 

Valve dynamic 

1..6 

Valv delay 

30..255 

200 

 

Heat source 

range 

fact. 

Support 

Off/On 

On 

Histeresis 

1..30K 

Min. temperature 

10..70

ºC 

30 

Max. temperature 

50..90

ºC 

75 

Buffer 

Yes/No 

No 

Buffer preset temp.* 

30..75

ºC 

60 

HW priority 

Yes/No 

No 

Cooling temp. 

80..100

ºC  88 

OFF by thermostat* 

Yes/No 

No 

Increrase temp. 

1..20

ºC 

 

 

 

Protection 

range 

fact. 

Return sensor 

Off/On 

Off 

Min. temperature* 

30..65

ºC 

40 

Histeresis* 

2..15K 

Closing the valve* 

0..50% 

10 

Frost protection 

Off/On 

On 

Frost protection delay* 

1..10h 

Frost protection temp.* 

5..10

ºC 

 
*  not  available  when  not  connected  the 
corresponding sensor, the parameter is hidden or 
is not appropriate settings in the menu. 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание WT100

Страница 1: ...WEATHER CONTROLLER WT100 FOR CONTROL TEMPERATURE HEATING CIRCUIT OPERATIONS AND INSTALLATION MANUAL VERSION 1 4 SOFTWARE VERSION v01 XX XX 03 2018...

Страница 2: ...2...

Страница 3: ...THE CONTROLLER 15 ENVIRONMENTAL CONDITIONS 15 INSTALLATION REQUIREMENTS 15 EXTERNAL CIRCUITS CONNECTION 16 CONNECTING ELECTRICAL SYSTEM 17 FIXING THE EXTERNAL WIRES 17 CONNECTION OF TEMPERATURE SENSO...

Страница 4: ...t in case of failure it can be a source of sparks or high temperature which surrounded by ashes or flammable gases can cause fire or explosion Modification of the programmed parameters should be made...

Страница 5: ...to observe these instructions Documentation storage Please keep this operation and assembly manual and other valid documentation in a safe place for future reference In case of moving or selling the d...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL WT100...

Страница 8: ...ixer actuator position ON open OFF closed STOP off 5 working heat source boiler switched on 6 information from the room thermostat No icon the thermostat is off Heating room temperature below the pres...

Страница 9: ...mperature In periods of night heating circuit is completely turns off The frost protection function remains active as long as it is enabled in the Service menu Schedule The time intervals allow the in...

Страница 10: ...turned on automatically using the Auto parameter including temperature settings for the Summer mode ON temp and Summer mode OFF temp General settings In general settings can change the settings date t...

Страница 11: ...INSTALLATION MANUAL AND SERVICE SETTINGS WT100...

Страница 12: ...vice settings Room thermostat Start pump temp 55 C 20 C Service settings Heating circuit Return sensor ON Service settings Protection In order to improve water flow in gravitational circuit of the boi...

Страница 13: ...source with S ON OFF contact gas or oil boiler 2 relief valve different pressure 3 hydraulic coupling RECOMMENDED SETTINGS Parameter Setting MENU Kind of the system Radiators system Service settings...

Страница 14: ...y valve actuator 1 heat source with S ON OFF contact gas or oil boiler 2 relief valve different pressure 3 hydraulic coupling RECOMMENDED SETTINGS Parameter Setting MENU Kind of the system Underfloor...

Страница 15: ...unit casing disconnect power supply The unit installation must be done at disconnected voltage Controller must be installed by qualified and authorized technician in accordance with EN 60335 1 standa...

Страница 16: ...50Hz P CH pump SM mixer actuator S contact to operate the heating source type ON OFF FU time delay subminiature fuse The terminals for hazardous voltage COM NO ZLo ZN ZLc PN PL L N The terminals safe...

Страница 17: ...supply 230V to terminals for sensors will damage the regulator and creates risk of an electric shock Tips of the connected wires especially power leads must be secured against splitting by means of in...

Страница 18: ...e may be shown Minimum length between those wires should be 100mm It is not acceptable to allow for contact betweens wires of the sensors and hot parts of the boiler and heating installation Wires of...

Страница 19: ...pump in the parameter Off by thermostat The values of the parameters must be chosen so that when of working the room thermostat contact opening the temperature in the room dropped Connecting a heat so...

Страница 20: ...ease of work mode 0 15K 10 Decrease of thermostat 0 30K 10 OFF by thermostat Yes No Yes Start pump temp 10 70 C 35 Min temperature 5 40 C 20 Max temperature 20 50 C 40 Valve full opening time 60 200s...

Страница 21: ...ning the thermostat Preset temperature of water inside the heating circuit is not changed if Decrease of thermostat 0 Parameter disappears when Room thermostat OFF OFF by thermostat Stopping the flow...

Страница 22: ...an accuracy of 1 Frost protection ON or OFF frost protection function Frost protection delay Time delay for enable frost protection function Description later in this manual Frost protection temp The...

Страница 23: ...move In this setup it is possible to connect a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessa...

Страница 24: ...vices settings Protection Frost protection Description of frost protection against the external temperature sensor readings When the external temperature drops below 3 C an Frost protection delay e g...

Страница 25: ...5 C Technical data Power 230V 50Hz Maximum current consumption with loaded outputs 3 3 A Maximum current consumption without loaded outputs 0 02A Output current Pump Mixer actuator ON Mixer actuator O...

Страница 26: ......

Страница 27: ......

Страница 28: ...SALUS Controls ul Rolna 4 43 262 Kobielice Poland www salus controls pl...

Отзывы: