Tel: 886.909 602 109 Email: [email protected]
30
four-core aviation sockets at both ends.
2) Power on the receiver and set the receiving mode in external input mode
, set the
frequency of the receiver corresponding with the transmitter.
3) Read the reference value of the signal strength: Place the receiving clamp around
the red cable of the direct connection lead or the start end of the target cable. Adjust
the gain value to bring the signal strength value about 800. Do not change the gain
value; remember the current signal strength as a reference value.
4) Arrive at the position being tested. Place the clamp around the exposed part of the
target cable and the cable with the strongest signal strength that is equal to the
reference value approximately is the target cable to be recognized. If the signal
strength of cables is all weak, it indicates that the cable to be recognized is not here.