ENGLISH
15
connection
of
a
400/690V
motor
on
a
690V
power
supply
might
drive
to
motor
destruction
if
terminal
strip
are
positioned
in
a
wrong
way.
Electrical
connection
should
be
performed
by
qualified
personnel
only
having
necessary
agreements
and
in
compliance
with
local,
national
and
international
regulations.
Equipments
used
in
an
ATEX
zone
will
be
connected
in
compliance
with
CEI60079
‐
14.
It
is
the
responsibility
of
the
end
user
to
select
proper
type
and
size
of
electric
cable.
Respect
motor
manufacturer
instructions
to
make
electric
motor
connection
(refer
to
the
instructions
supplied
with
the
motor.
they
are
usually
indicated
inside
motor
junction
box).
Sensors
will
be
connected
in
compliance
with
the
instructions
given
in
dedicated
instruction
manual.
7.3.1
TERMINAL
STRIP
POSITIONNING
FOR
STAR
(Y)
AND
DELTA
(
)
CONNECTION
(MULTI
‐
VOLTAGES
ELECTRIC
MOTORS)
Multi
‐
voltage
winding
for
voltages
230/400V
and
400/690V
:
6
wiring
terminals
:
To
change
motor
direction
of
rotation
reverse
two
phases
on
wiring
terminals.
Connection
of
earthing
terminal
is
mandatory.
7.3.2
LOWER
VOLTAGE
:
CONNECTION
Voltage
:
U
7.3.3
HIGHER
VOLTAGE
:
Y
CONNECTION
Voltage
:
U
3
7.3.4
Y
/
STARTER
:
Grounding
of
the
complete
pumpset
will
be
performed
with
special
care.
Earthing
will
avoid
any
electrostatic
accumulation
in
components
of
the
pumpset.
Each
part
of
the
pumpset
should
be
connected
to
earth
with
a
correctly
calibrated
bonding
strap
or
cable
(motor
winding,
motor
frame,
coupling
guard,
pump
baseframe).
7.4
USE
OF
A
FREQUENCY
INVERTER
When
pump
is
used
with
a
variable
speed
drive,
make
sure
that
the
frequency
inverter
instructions
and
operating
manual
is
available
and
known.
The
electric
motor
that
is
supplied
with
the
pump
may
be
connected
under
conditions
to
a
VSD.
Variable
speed
will
be
used
to
reach
pump
required
duty
point
on
site.
To
ensure
a
reliable
use
of
the
equipment
a
few
precautions
should
be
taken
:
Electrical
requirements
:
Variable
frequency
drive
will
not
generate
voltage
peak
higher
than
850V
(motor
phases
isolation)
and
dU/dt
values
higher
than
2500
V/µs
(winding
isolation).
If
those
values
can
be
reached,
a
filter
should
be
installed
:
ask
inverter
manufacturer
for
proper
selection
and
motor
manufacturer
for
limit
values.
Choose
a
vector
control
inverter
or
use
a
quadratic
V/F
control
inverter.
Check
that
motor
nominal
voltage
is
never
exceeded.
Power
supply
cable
should
comply
to
ATEX
regulation.
Ensure
that
motor
winding
is
equipped
with
CTP
temperature
sensors
inside.
A
physical
barrier
should
separate
power
supply
cables
and
low
voltage
cables
to
avoid
analog
signal
distortion.
Hydraulic
requirements
:
A
dedicated
suction
pipe
should
be
dedicated
to
each
pump
used
with
a
negative
suction
head
(suction
lift).
Check
that
the
pump
NPSH
R
at
minimum
speed
is
always
lower
than
system
NPSH
A
.
Mechanical
requirements
:
Lower
speed
should
not
fall
under
40%
of
pump
nominal
speed
to
avoid
any
vibrations
and
an
unstable
flow.
The
harmonic
currents
that
are
created
by
the
VSD
pass
through
motor
ball
bearings.
Standard
ball
bearings
can
be
used
up
to
55KW.
For
higher
installed
power
(see
engraved
power
on
motor
name
plate),
the
motor
should
be
equipped
with
isolated
ball
bearings
(specific
ball
bearing)
or
with
isolated
bearing
housing
(and
standard
ball
bearing).
8
START
‐
UP
8.1
PRE
‐
COMMISSIONING
If
the
pump
is
installed
in
a
potentially
explosive
atmosphere
or
when
dangerous
or
polluting
fluids
are
pumped,
it
is
advised
(Zone
2)
or
requested
(zone
1)
to
install
additional
protection
devices.