7.  Maintenance, warranty 

and service.

7.1.  Maintenance of the battery.

• 

Pay attention to the safety instructions regarding battery and 

the stated in section 1.2.3.3 

• 

The equipment from 

SPS.ADVANCE RT

 series only requires 

a minimum maintenance. The used battery in the standard 

models is lead acid, sealed, VRLA and maintenance free. 

These models require a minimum of reparations. The only re-

quirement is to charge the UPS regularly, in order to prolong 

the battery lifetime. Meanwhile, it is connected to the power 

supply, never mind if the UPS is ON or OFF, it will keep the 

batteries charged.

• 

The UPS has to be charged once, every 4 or 6 months if it 

has not been used for long time.

• 

In hot areas, battery has to be charged every 2 months. The 

charging time has to be 12 hours as minimum.

• 

Under normal conditions, the battery lifetime is from 3 to 5 

years 25º C. In case that the battery was not in good condi-

tions, it has to be replaced before. This replacement has to 
be done by qualified staff.

• 

Always replace them with the same quantity and type.

• 

Do not replace one battery only. All batteries have to be re-

placed at the same time and following the instructions of the 

manufacturer.

• 

Usually, the batteries should be charged and discharged 

every 4 or 6 months. The charging would be started after a 

UPS shutdown due to a low battery (discharging). Charging 

time for standard UPS should be 12 hours as minimum.

7.1.1.  Notes for installing and replacing 

the batteries. 

• 

If it is needed to replace the connection of any wire, purchase 

original parts through authorised distributors or service cen-

tres in order to avoid overheating or sparks with risk of fire 

because the size could not be enough.

• 

Do not short the + and - poles of the batteries, there is risk of 

fire or electrocution.

• 

Be sure that there is no voltage before touching the batteries. 

Battery circuit is not isolated from the input circuit. Hazardous 

voltages can be found between the battery and earth termi-

nals.

• 

Even with the input circuit breaker switch from protection 

panel  is turned off, the internal parts of the UPS are still con-

nected to the batteries, so there are hazardous voltages in-

side.
Therefore, before doing any reparation or maintenance task, 

the internal battery fuses and/or the interlink connections be-

tween them and the UPS, have to be removed.

• 

Batteries have hazardous voltages. The battery main-

tenance and replacement have to be done by qualified 

personnel and familiarised with them. Nobody else can ma-

nipulate them.

7.2.  UPS Trouble Shooting guide.

If the UPS doesn't work properly, check the information given 
by the LCD of the control panel, according to the models and 
power of the equipment. Try to solve the problem by means 
of the established steps in the tables 11 and 12. In case the 
problem persists, consult with our Service and Technical Sup-
port S.T.S..
When it is needed to contact with our Service and Technical Sup-
port S.T.S. , provide the following information:

• 

UPS model and serial number.

• 

Date when the problem occurred.

• 

Complete description of the problem, including the informa-

tion given by the LCD panel and the status of the alarms.

• 

Power supply condition, type of load and the level connected 

to the UPS, ambient temperature, cooling conditions.

• 

Information of the batteries (capacity and battery quantity), if 

the equipment is (B0) or (B1) -with external batteries-.

• 

Other informations that you may think that they are important.

7.2.1.  FAQ. Acoustic alarms.

Acoustic alarm

Possible cause

Solution

Beep every 4 seconds.

The equipment is on battery mode

Check the input voltage and/or the power cord is connected to the AC 

wall outlet.

Beep every  second with LCD from control 

panel with "BATL" indication.

Low battery voltage.

Save the taks in process and shutdown the load/s and the UPS.

Beep every second with LCD from control 

panel with "OVLD" indication.

Overload at the output.

Check the load level connected at the output and proceed to remove 

the exceeded one, keeping in mind the critical loads.

LCD panel is still on red colour 

UPS fault.

Consult with the S.T.S..

Tabla 11. 

Acoustic alarms.

Содержание SPS.ADVANCE RT series

Страница 1: ...PLY UPS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SPS ADVANCE RT series UNINTERRUPTIBLE P...

Страница 2: ......

Страница 3: ...IEC outlets 4 3 3 Connection of the external batteries extended back up time 4 3 4 Connection of main input earth terminal and the earth bonding terminal 4 3 5 EPO terminals in UPSs 1kVA Emergency Pow...

Страница 4: ...s for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic in structions an...

Страница 5: ...ive terminal for the load earth connection When an outgoing dis tribution is done i e power strips it is essential that they have an earth terminal connected to each one of them It is essential that t...

Страница 6: ...ven pack aged the equipment will be left for a minimum time of two hours in the new location before making any action with the purpose of adapting it to the new environmental conditions and avoid the...

Страница 7: ...battery cabinet to the equipment respect the cable s polarity and colour red positive black negative indicated in the manual and in the cor responding labelling Wear rubber gloves and shoes Use tools...

Страница 8: ...tive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s us...

Страница 9: ...ment can be checked Act in accordance with the installation Front virew ADVANCE RT Fixing screws Plastic beauty front Fixing screws Plastic beauty front Control panel with LCD Plastic beauty front Fro...

Страница 10: ...AC power supply Earth connection for battery module Output connector with M dem ADSL Fax protection Connector for external EPO Smart slot protection cover Fan IEC outlets LS2 Input connector for modem...

Страница 11: ...of strings in parallel Omitted for one 0 Battery module without them but the needed accessories to install them ADV RT Series of the battery module MOD BAT Battery module i Note relative to the batter...

Страница 12: ...from the batteries through the inverter for a determined time depending on the model battery charge level and the own load connected at the output For models higher than 1000 VA it is possible to inc...

Страница 13: ...olling and management at the manager system dis posal This facility is got through the SNMP adaptor which is well known by the main software and hardware manufacturers The available SNMP option for SP...

Страница 14: ...c isolation transformer as standard as an option or either in stalled by yourself either at the UPS input or output or at all of them protections against indirect contact has to be fitted in residual...

Страница 15: ...als therefore they should be disposed according to current regulations We recom mend to keep the packaging in case its use is necessary in the future Proceed as follows Cut the strips of cardboard enc...

Страница 16: ...wise B and insert it again into the beautiful front cover till click it C Check the correct closing of the fixing nails Put the beautiful front cover back in the reverse way as its removing see sectio...

Страница 17: ...ing with ex tended back up time battery module In the side of each front cover there are the K trims as a notch to go the cables through it with the battery modules Break the needed trims to pass the...

Страница 18: ...igure 9 For higher quantity of modules reproduce the connection procedure among them All models can be installed in a 19 rack cabinet attending the height of each one of them is 2 units Proceed as fol...

Страница 19: ...utlets As this is a device with class I protection against elec tric shocks it is essential to install a protective earth conductor connect earth Connect the conductor to the terminal before connectin...

Страница 20: ...rmally closed NC Less punctual cases it is not recommended to use this type of connection due to the function of the EPO button because it would not work in case of any of the two cables that goes fro...

Страница 21: ...the equipment labelled as Input Connect the own modem ADSL Fax to RJ45 connector of the equipment labelled as Output 4 3 7 Software Free software download WinPower WinPower is a UPS monitoring softwa...

Страница 22: ...part from sensi tive ones are required to be connected like laser printers or CRT monitors keep in mind the start inrush currents of these peripherals in order to avoid that the equipment becomes bloc...

Страница 23: ...from the nominal and takes as a default value the wrong one Check the frequency in the control panel and repeat the procedure if this circumstance would occur 5 2 2 UPS start up with mains present For...

Страница 24: ...on stabilizer mode Blue BATT Warning UPS working on battery mode Blue BTOP Warning Battery disconnected Red TEST Warning UPS working on battery in life function test Blue OPVH Fault Battery mode with...

Страница 25: ...the possible se lectable variables or values Code Description Values OPV Output voltage selection 220 220V 230 230V 240 240V AV Input voltage type 000 Normal range 001 Wide range 002 Gen set EBM Exte...

Страница 26: ...ments stated in table 10 and go forward or backward till reaching EBM 3 Validate the configuration element When the LCD panel displays EBM press the key for more than one second to enter into the elem...

Страница 27: ...the battery and earth termi nals Even with the input circuit breaker switch from protection panel is turned off the internal parts of the UPS are still con nected to the batteries so there are hazardo...

Страница 28: ...company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence installation and or inadequate testing tentative of repa...

Страница 29: ...reventive and corrective maintenance contracts is pos sible to determine the intervention timetable and response times as well as exclusion or inclusion parts in partial or total way with the purpose...

Страница 30: ...r kVA 0 750 1 1 5 2 3 Power kVW 0 675 0 900 1 350 1 8 2 7 Wave shape Pure sinewave Nominal voltage 220 230 240 V AC selectable Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD...

Страница 31: ...l loads always flow in the same direction from the highest potential point to the lowest one Although usually the direct current is identified with the constant cur rent for example the one supplied b...

Страница 32: ...agni tude and frequency by the user or the designer Rectifier In electronic a rectifier is the element or circuit that allows to convert the alternating current into direct cur rent This is done by re...

Страница 33: ...33 SALICRU...

Страница 34: ...34 USER MANUAL...

Страница 35: ...35 SALICRU...

Страница 36: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Отзывы: