26
2.- Select the configuration elements.
Press the key
to select the configurable elements
stated in table 10 and go forward or backward till reaching
"LS1" or "LS2" as it is required.
3.- Validate the configuration element.
When the LCD panel displays "LS1" or "LS2", press the
key
for more than one second to enter into the ele-
ment to set. The values of the variables blink (blinking
mode).
4.- Select the configuration value.
Press the key
to select the configuration value. Se-
lect the value (001) or (000) to set the desired IEC outlet
group, as turned on or off respectively.
5.- Confirm the configuration.
Press the key
for one second, the UPS will return to
the previous point 2.
6.- Escape from setting mode.
Press the key
for 3 seconds or the key
for 0,5
seconds, to escape from the setting mode.
6.1.6.3. Setting the UPS to connect it with "n"
battery modules.
•
In order to be sure that the LCD panel displays the correct
remaining capacity of the batteries, the available quantity of
battery modules has to be set and updated when facing any
modification, otherwise the displayed data will not be real.
Models ≤ 1 kVA do not have connectors to extend the
back up time.
•
Proceed as follows:
1.- Enter into the configuration mode.
Press the key
for more than 3 seconds and the UPS
will shift to setting mode.
2.- Select the configuration elements.
Press the key
to select the configurable elements
stated in table 10 and go forward or backward till reaching
"EBM".
3.- Validate the configuration element.
When the LCD panel displays "EBM", press the key
for more than one second to enter into the element to set.
4.- Select the configuration value.
Press the key
to select the quantity of battery mod-
ules available for the UPS.
5.- Confirm the configuration.
Press the key
for one second, the UPS will return to
the previous point 2.
6.- Escape from setting mode.
Press the key
for 3 seconds or the key
for 0,5
seconds, to escape from the setting mode.
6.1.6.4. Setting the "Green" function.
•
If this function is activated, the UPS disable the output when
it is on battery mode when it is not detected a minimum of
consumption. By default, this feature is deactivated, if it is
needed to modify it, proceed as follows:
1.- Enter into the configuration mode.
Press the key
for more than 3 seconds and the UPS
will shift to setting mode.
2.- Select the configuration elements.
Press the key
to select the configurable elements stated
in table 10 and go forward or backward till reaching "GF".
3.- Validate the configuration element.
When the LCD panel displays "GF", press the key
for
more than one second to enter into the element to set.
4.- Select the configuration value.
Press the key
to select the configuration value.
Select the value (001) to activate function.
5.- Confirm the configuration.
Press the key
for one second, the UPS will return to
the previous point 2.
6.- Escape from setting mode.
Press the key
for 3 seconds or the key
for 0,5
seconds, to escape from the setting mode.