The UPS must be installed in such a way as to ensure its
serviceability and allow correct air flow as much as possible.
Regarding minimum distances from walls, the recommended
values are indicated below.
A
(mm)
B
(mm)
C
(mm)
D
(mm)
UPS with internal batteries
Recommended spaces
50
1200
600
600
Minimum spaces
0
1200
600
400
UPS with external battery cabinet
Recommended spaces
50
1200
400
600
Minimum spaces
0
1200
0
400
Tabla 2.
Minimum and recommended spaces for
80... 160 kVA devices.
A
(mm)
B
(mm)
C
(mm)
D
(mm)
Recommended spaces
50
1200
50
600
Minimum spaces
0
1200
0
400
Tabla 3.
Minimum and recommended spaces for
200... 300 kVA devices.
A
(mm)
B
(mm)
C
(mm)
D
(mm)
Recommended spaces
50
1200
50
600
Minimum spaces
0
1200
0
400
Tabla 4.
Minimum and recommended spaces for 400 kVA
devices.
The following table shows the volume of air required for
optimum ventilation and cooling of the UPS.
Power (kVA)
80
100
125
160
200
250
300
400
Air volume
(m
3
/h)
1200
1200
1500
1500
1800
2200
2300
4000
Tabla 5.
Volume of air required to properly ventilate the
UPS.
5.1.8. Environmental conditions of the installation.
Air is classified in standard EN 60721-3-3 (Classification of
groups of environmental parameters and their severities,
stationary use at non-weatherprotected locations), according
to weather and biological conditions, as well as mechanically
and chemically active substances.
The installation site must meet certain requirements to ensure
compliance with the design conditions of the UPS.
•
Weather conditions according to technical specifications:
ENVIRONMENTAL PARAMETER
VALUES
Minimum operating temperature (°C)
-10
Maximum operating temperature (°C)
+40
Minimum relative humidity (%)
5
Maximum relative humidity (%)
95
Condensation
NO
Precipitation with wind (water, snow, hail, etc.)
NO
Non-rain water
NO
Ice formation
NO
Tabla 6.
Environmental conditions of the UPS.
•
Classification of biological conditions (EN 60721-3-3):
ENVIRONMENTAL
PARAMETER
CLASS
3B1
3B2
3B3
Flora
NO
Presence of mould, fungi, etc.
Fauna
NO
Presence of rodents or other
animals that may damage the
device, excluding termites.
Tabla 7.
Biological conditions.
•
Classification of mechanically active substances
(EN 60721-3-3):
ENVIRONMENTAL PARAMETER
CLASS
3S1
3S2
3S3
3S4
Sand (mg/m
3
).
No
30
300
3000
Dust (suspension) (mg/m
3
).
0.01
0.2
0.4
4.0
Dust (sedimentation) (mg/(m
2
·h)).
0.4
1.5
15
40
Places where precautions have been taken to minimise the presence of dust. Places away from sources
of dust or sand.
X
Places without precautions to minimise the presence of sand or dust, but not near sources of sand or dust.
X
Places close to sources of sand or dust.
X
Places near work sites where sand or dust is produced, or in geographical areas with high presence of
wind-borne sand or dust in the air.
X
Tabla 8.
Classification of mechanically active substances.
Содержание SLC X-PERT 100
Страница 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Страница 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Страница 18: ...18 SALICRU 880 1978 947 Air outlet openings Front air inlet openings Fig 16 Dimensions of 200 300 kVA devices...
Страница 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Страница 60: ...60 SALICRU...
Страница 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...