8
| EN
SMARTY XP S300 v2022.1
4.3. TECHNICAL
DATA
SMARTY
2XP S300
3XP S300
4XP S300
Exhaust air fan
phase/voltage
[50 Hz/VAC]
1/230
1/230
1/230
SRZHUFXUUHQW
[kW/A]
0,05/0,4
0,09/0,75
0,17/1,35
speed
[min
-1
]
4525
3200
4120
control input
[VDC]
0-10
0-10
0-10
protection class
IP 44
IP 54
IP54
Supply air fan
phase/voltage
[50 Hz/VAC]
1/230
1/230
1/230
SRZHUFXUUHQW
[kW/A]
0,05/0,4
0,09/0,75
0,17/1,35
speed
[min
-1
]
4525
3200
4120
control input
[VDC]
0-10
0-10
0-10
protection class
IP 44
IP 54
IP54
7RWDOSRZHUFXUUHQWFRQVXPSWLRQ
[kW/A]
0,15/1,02
0,22/1,72
0,39/2,92
Automatic control integrated
S300
S300
S300
,QVXODWLRQRIZDOOV
[mm]
20
30
30
([KDXVWDLU¿OWHU
(class, dimensions LxWxH)
[mm]
03/[[&RDUVH 03/[[&RDUVH 03/[[&RDUVH
6XSSO\DLU¿OWHU
(class, dimensions LxWxH)
[mm]
03/[[&RDUVH 03/[[&RDUVH 03/[[&RDUVH
Device protection class
IP 34
IP 34
IP-34
According to EN 13141-7.
Acoustic data: check the product page on https://select.salda.lt
Not suitable for installation in living rooms: additional noise insulation required.
4.4. OPERATING
CONDITIONS
SMARTY
2X P
3X P
4X P
2XWGRRUDLUWHPSZLWKRXWIURVWSURWHFWLRQ
-2 .. 40 °C
-2 .. 40 °C
-2 .. 40 °C
Ambient air temp.
5 .. 40
o
C
5 .. 40
o
C
5 .. 40
o
C
Min extracted air temp
16
o
C
16
o
C
16
o
C
Max extracted air humidity
Max. ambient air humidity
Operation environment
Indoors
Indoors
Indoors
4.5. STANDART PACKAGE OF COMPONENTS
SMARTY
2XP
3XP
4XP
Key M4 Z-type
1
1
1
Outlet pipe G3/8
1
1
1
Anti-vibration rubber 313508000
4
4
4
BFG bush caps
8
8
8
Содержание Smarty 2X P S300
Страница 1: ...SMARTY XP S300 EN MOUNTING AND INSTALLATION INSTRUCTION...
Страница 19: ...EN 19 SMARTY XP S300 v2022 1 Smarty 2X P S300 E1 Smarty 3 4XP S300 E2...
Страница 26: ...26 EN SMARTY XP S300 v2022 1 8 9 CO2 CONCENTRATION ACCORDING TO PETTENKOFER LIMIT...
Страница 27: ...EN 27 SMARTY XP S300 v2022 1 9 PINOUT OF THE CONTROLLER Figure 9 1 S300 controller...
Страница 39: ...39 SMARTY XP S300 v2022 1...