EN |
35
SMARTY XP S300 v2022.1
14. ECODESIGN DATA TABLE
MODEL
SMARTY 2XP S300
Climate
zone
Control typology
Control
factor
6SHFL¿FHQHUJ\
consumption
6(&
SEC Class
AEC
AHS
[ kWh/m²/a ]
[ kWh/a ]
[ kWh/a ]
Average
Clock control (standard)
0,95
-35,1
A
418
4486
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-37,4
A
344
4530
Cold
Clock control (standard)
0,95
-72,6
A+
955
8776
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-75,3
A+
881
8861
Warm
Clock control (standard)
0,95
-11,0
E
373
2028
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-13,0
E
299
2048
Declared typology
Bidirectional
Type of drive installed (fan)
Variable
Type of heat recovery system
Recuperative
7KHUPDOHႈFLHQF\RIKHDWUHFRYHU\
>@
86,3
0D[LPXPÀRZUDWH
[ m
3
/h ]
218
(OHFWULFSRZHULQSXWRIWKHIDQGULYHDWPD[LPXPÀRZUDWH
[ W ]
104
6RXQGSRZHUOHYHO/ZD
[ dB(A) ]
49
5HIHUHQFHÀRZ
[ m
3
/s ]
0,042
5HIHUHQFHSUHVVXUHGLႇHUHQFH
[ Pa ]
50
SPI
[ W/(m
3
/h) ]
0,33
Declared maximum internal leakage rates
>@
1,2
Declared maximum external leakage rates
>@
1,2
3RVVLWLRQDQGGHVFULSWLRQRIYLVXDO¿OWHUZDUQLQJIRU598¶V
Timer
ErP Compliance
2018
Internet address for disassembly instructions
https://select.salda.lt
MODEL
SMARTY 3XP S300
Climate
zone
Control typology
Control
factor
6SHFL¿FHQHUJ\
consumption
6(&
SEC Class
AEC
AHS
[ kWh/m²/a ]
[ kWh/a ]
[ kWh/a ]
Average
Clock control (standard)
0,95
-36,1
A
362
4447
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-38,2
A
298
4494
Cold
Clock control (standard)
0,95
-73,3
A+
899
8699
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-75,8
A+
835
8792
Warm
Clock control (standard)
0,95
-12,2
E
317
2011
&HQWUDOGHPDQGFRQWURORSWZLWKVHQVRU
0,85
-14,0
E
253
2032
Declared typology
Bidirectional
Type of drive installed (fan)
Variable
Type of heat recovery system
Recuperative
7KHUPDOHႈFLHQF\RIKHDWUHFRYHU\
>@
85
0D[LPXPÀRZUDWH
[ m
3
/h ]
395
(OHFWULFSRZHULQSXWRIWKHIDQGULYHDWPD[LPXPÀRZUDWH
[ W ]
174
6RXQGSRZHUOHYHO/ZD
[ dB(A) ]
45
5HIHUHQFHÀRZ
[ m
3
/s ]
0,077
5HIHUHQFHSUHVVXUHGLႇHUHQFH
[ Pa ]
50
SPI
[ W/(m
3
/h) ]
0,28
Declared maximum internal leakage rates
>@
1,2
Declared maximum external leakage rates
>@
1,2
3RVVLWLRQDQGGHVFULSWLRQRIYLVXDO¿OWHUZDUQLQJIRU598¶V
Timer
ErP Compliance
2018
Internet address for disassembly instructions
https://select.salda.lt
Содержание Smarty 2X P S300
Страница 1: ...SMARTY XP S300 EN MOUNTING AND INSTALLATION INSTRUCTION...
Страница 19: ...EN 19 SMARTY XP S300 v2022 1 Smarty 2X P S300 E1 Smarty 3 4XP S300 E2...
Страница 26: ...26 EN SMARTY XP S300 v2022 1 8 9 CO2 CONCENTRATION ACCORDING TO PETTENKOFER LIMIT...
Страница 27: ...EN 27 SMARTY XP S300 v2022 1 9 PINOUT OF THE CONTROLLER Figure 9 1 S300 controller...
Страница 39: ...39 SMARTY XP S300 v2022 1...