22
Smarty 2R VE
www.salda.lt
Code
Alarm/warning information
A.01
Broken rotor belt
A.02
Fire place protection is activated
A.03
Humidity control function is activated
A.04
Anti-frost protection of plate heat exchanger is activated
A.05
Anti-frost protection of plate heat exchanger. The system is off.
A.06
Anti-frost protection of plate heat exchanger (pressure relay). The system is off.
A.07
Anti-frost protection of water heater. The system is off.
A.08
Supply air temperature is too low
A.09
Supply air temperature is too high
Nr.
Name
Possible values
Default
value
P
.
01
Sleep mode
0 - Off
1 - 99 sleeping time in seconds
0
P
.
02
Sound
0: Off
1: 1 –9 sound tone
2
P
.
03
Supply air temperature display
0: Not shown
1: Shown interchangeably with the set temp
0
P
.
04
CO
2
required (ppm)*
0 – 99 x10ppm
20 x10
P
.
05
CO
2
allowed difference*
0 – 99 x10ppm
5 x 10
P
.
06
Filtrer timer
Shows the period that passed after the change of the filters.
0
• Temperature from 15 to 30
o
C may be set by remote controller.
Note:
Temperature of MCB controller can be adjusted from 0 up to 40
o
C (it depends on MCB settings).
• Possible alternate display of supply and set air temperature display (5 seconds - set air temperature display, 2 seconds - supply air temperature).
• In order to reach user menu, press down both B2 and B3 for 3 seconds.
• In user menu, settings of menu items (P.01, P.02 etc.) are displayed sequentially.
• Menu item is selected using elements B4 and B6.
• Pressing B5 element value of selected parameter is shown and can be changed using elements by B4 and B6.
• Press B5 to save the parameter and return to menu.
• Due to limitations of segment display, values of the element P.04 and P.05 are shown in division by 10, i.e. if 20 is displayed, it means that real value is
20 x 10 = 200.
• Touch element B1 to exit menu.
• Left time for changing filters can be monitored in users menu.
• User can reset the timer. P.06 - hold for 5 seconds item B5.
• User is warned about filter change, cancelling the warning filter timer is reset automatically.
Selecting 4 pre-set speeds:
• 0 speed – stand-by mode;
• 1 speed – building protection mode;
• 2 speed – economic mode;
• 3 speed – comfort mode.
Each mode (except stand-by) has its own temperature setting. The temperature setting is made by selecting the desired mode. In economic and standby
mode temperature back-up can be turned off. Reducing temperature setting until the segment display shows the symbol “-.-” meaning that temperature
back-up is turned off in the selected mode. It is impossible to turn off temperature back-up in comfort mode.
BOOST function period is being read form control board during the activation moment of the function. After manual change of the time with the control
panel, the left time is being set automatically in the control board.
*only for CO
2
sensor, which is connected to control panel.
B1
L2-L7
CO
2
blow off
By pressing B1 indication
„CO2“is not shown tempo-
rary.
L2, L3 and L7 are blinking, L4, L5, L6 are shining. Split screen shows “
CO2
”.
By pressing B1 indication “
CO2
” is not shown for one minute, thus permitting to
adjust temperature and fan settings.
B2 B3 B5
On/off
“Child safety feature”
Press down B3, B2 and B5
for 2 seconds.
Non active elements B1, B4 and B6. After pressing unavailable button, segment
display shows “−−−”