Commissioning

Before you finish

Fit pump inlet filters and vibration dampening feet.

 

It is CRITICAL to discharge water through the pump into a container using natural flow 

before connecting the pump to outlet pipework in order to ensure the air has been 

discharged from inlet pipework and pump chambers. This will not happen if the outlet 

pipework is connected to the pump. The best method is:-

•  Connect discharge pipework, not outlet pipes.

• 

Check that all the AV coupler isolating valves are open.

•  Fill system. Check for leaks.

  DO NOT RUN PUMP DRY – to do so will cause irreparable damage to your pump and will 

invalidate your warranty.

•  Open shower mixer valve/system outlets to maximum hot and cold to check the natural 

flow (unpumped) MUST be at least 1 litre in 30 seconds per side and 2 litres in 30 seconds 

mixed for positive head pumps. 

•  Open hot water outlets fully for 5 to 6 seconds and then turn outlets off. Then open cold 

water outlets fully for 5 to 6 seconds and turn outlets off. If flow is poor and inconsistent 

repeat above steps until flow is steady.

•  Repeat 2-3 times

Negative head systems 

Negative head systems exist where insufficient natural flow of water goes to the outlet 

because either the outlet or the pipework to the outlet are above the height of the base of 

the cold water cistern. Most instances of negative head systems occur in loft conversions 

or where the cold water cistern sits on the joists in the loft. If the distance between the 

bottom of the cold water cistern and the highest point in the system after the pump is 2 

feet (610mm) or less, it is also possible that a universal pump will be required. Salamander’s 

universal range of pumps activate the pump automatically even where insufficient natural 

flow exists.
UK CT pumps suitable for negative head operation are: 

CT FORCE 15 TU, 20 TU, 20 SU, 30 TU and 30 SU, and CT Bathroom 60BU & 80BU. 
Irish CT pumps suitable for negative head operation are: 

CT FORCE 15 ITU, 20 ITU, 20 ISU, 30 ITU and 30 ISU, and CT Xtra 64HU, 69HU & 84HU.

Outlet

Outlet

Vent and

other services

Usable

capacity

Fit an 

equilibrium

ball valve

Inlet

MAX

65°C

The hot connection

must be by an 

approved top or

side entry flange

(Figure 3)

Negative

Head

If any pipe work to an outlet 

is taken to within 610mm

of tank, the installation will need

to be fitted with a universal pump

Inlet

610mm

(2 feet)

The hot connection must be via an 

approved side or top entry flange

MAX

65°C

Outlet

Outlet

Inlet

Inlet

Figure 8. Negative head system

The hot connection 

must be by an 

approved method

Содержание CT Force

Страница 1: ...Pump installation and warranty guide for the CT range of pumps CT Force CT Xtra and CT Bathroom ISSUE H JAN 2019 Models shown CT FORCE 15TU CT50 Xtra CT60B ...

Страница 2: ...rouble free system It is therefore important to read these instructions thoroughly and ensure you comply with them Incorrect fitting will invalidate the warranty If your installation is complicated or you have any questions please CONSULTTHE PUMPWISE TECHNICAL HELPLINE IMMEDIATELY on 0191 516 2002 01844 3212 ROI DO NOT REMOVE YOUR PUMP FROM THE SYSTEM WITHOUT FIRST RINGING PUMPWISE ON 0191 516 200...

Страница 3: ...inder within 5m of measured pipe 2m MAX of 15mm pipework on inlet connections may be used Allow 100mm on all sides for ventilation Ensure pump is protected from frost If servicing two or more bathrooms cold water supply to the cylinder must be in 28mm pipework Ensure adequate cold water storage 227 litres 50 gal per bathroom 364 litres 80 gal for one bathroom and one en suite Cold water supplies t...

Страница 4: ...T FORCE 20 PS 20 IPS 30 PS 30 IPS CT Xtra 55 55 59 85 85 89 are positive single impellor pumps Inlets and outlets must be vertical and plumbed appropriately It is essential to ensure that The cold stored water capacity is adequate for the entire household requirements eg minimum 136 litres 30 gal for shower only 227 litres 50 gal per bathroom or 364 litres 80 gal for one bathroom plus an en suite ...

Страница 5: ... pump is as close to the hot water cylinder as possible no more than 5m in measured pipework away 5 Mount the pump upright shaft horizontal not screwed down 6 An anti gravity loop AGL of at least 400mm ideally using swept bends must be used when the pump is sited above the dome of the hot water cylinder as it prevents air tracking up into the pump chamber and back siphoning of the water again crea...

Страница 6: ...ow of water goes to the outlet because either the outlet or the pipework to the outlet are above the height of the base of the cold water cistern Most instances of negative head systems occur in loft conversions or where the cold water cistern sits on the joists in the loft If the distance between the bottom of the cold water cistern and the highest point in the system after the pump is 2 feet 610...

Страница 7: ...e done during commissioning Step 2 Connecting the pump Use only Salamander supplied AV couplers to connect the pump All associated pipework MUST be thoroughly flushed before making final connections to the pump Fill the pump with water before connecting to the discharge pipework The in line strainers must be fitted to the hot and cold inlet supplies to the pump A Hose to pipework The anti vibratio...

Страница 8: ...ll valve is positioned above the cold feeds to the cylinder and to the pump aerated water is drawn into the pump as illustrated Chronic aeration of the pump occurs when this problem is combined with inadequate storage capacity and or when the volume of water is drawn by the pump and other services exceeds the refill rate and creates a vortex which draws air and possibly debris into the pump Cold s...

Страница 9: ...e g Aga solid fuel appliance or very crudely by the boiler thermostat a Salamander approved HWS TMV must be used Approved flanges cylinders The 22mm No Stop Essex and the other approved top entry flanges with extension pipes into the cylinder represent the best known means of ensuring minimal aeration of the hot supply water to the pump Please contact PumpWise on 0191 516 2002 for additional appro...

Страница 10: ... Fully automatic flow operated requiring 1ltr in 30 sec per side or 2ltr in 30 sec mixed Only applies to positive head pumps Temperature Maximum fluid temperature 65ºC Pump noise Salamander has engineered this product range to be as quiet as possible however no pump is completely silent Correct installation anti vibration couplers straight rubber feet fitted will minimise noise vibration and trans...

Страница 11: ... prior notice The CT Xtra and CT Bathroom ranges of pumps are fully WRAS approved CT Xtra has also been awarded Quiet Mark Part No Description Specification Performance Connection Type Pump Volumetrics Packed Pump Volumetrics Electrical Input Pump Type Pump Hoses Isolators Dimensions Dimensions CT FORCE Force 15PT Force 15IPT 1 5 Bar Twin End Positive Head Shower Pump 3A 110 1 1 130 1 3 150 1 5 22...

Страница 12: ...9 Xtra 2 5 Bar Single End Positive Head Shower Pump 3A 170 1 7 200 2 0 220 2 2 21mm 3 86 185 120 160 4 59 293 213 226 Fuse 230 1 50 Regenerative Pressure kPA Bar at 16ltr min Pressure kPA Bar at 8tr min Max pressure kPA Bar closed head BSP Push Fit Isolators intergrated into the hoses Weight Kg Length mm Width mm Height mm Weight Kg Length mm Width mm Height mm TechnicalSpecifications CTXtraH HU C...

Страница 13: ...vice Line Reduced intermittent flow Incorrect or no anti aeration flange fitted Fit appropriate anti aeration flange Insufficient gravity flow See above Blocked inlet filters Ensure that all filters and shower head are free from debris Couplers restricting flow Ensure that all AV couplers are straight and not bent or distorted Air in system Run system on full hot with pump switched off i e gravity...

Страница 14: ...ect to the terms and conditions below for the Warranty period s specified in paragraph 3 that the Company shall Repair or replace free of charge the product s specified on the Online Warranty Registration or Telephone Warranty Registration any component part thereof together referred as the equipment which shall in the opinion of the Company have proved defective by reason only of the Company s ma...

Страница 15: ...mpany 5 years from date of purchase provided the warranty is completed online or over the phone within 15 days of purchase Pumps purchased prior to 1st January 2016 come with 2 years warranty iii CT Xtra CT Bathroom UK only products manufactured by the Company 3 years from date of purchase provided the warranty registration is completed online or over the phone within 15 days of purchase iv CT Xtr...

Страница 16: ...28 29 Notes Notes ...

Страница 17: ...ter your warranty Apply online at www salamanderpumps co uk Apply by phone 0191 516 2002 Unit 2c Colima Avenue Enterprise Park West Sunderland SR5 3XE Get in touch we re here to help call us on 0191 516 2002 ...

Отзывы: