9

Commissioning

Before you finish

Fit pump inlet filters and vibration dampening feet.

 

It is CRITICAL to discharge water through the pump into a container using natural 

flow before connecting the pump to outlet pipework in order to ensure the air has 

been discharged from inlet pipework and pump chambers. This will not happen if 

the outlet pipework is connected to the pump. The best method is:-

•  Connect discharge pipework, not outlet pipes.

•  Check that all the AV coupler isolating valves are open.

•  Fill system. Check for leaks.

•  DO NOT RUN PUMP DRY – to do so will cause irreparable damage to your pump and 

will invalidate your warranty.

•  Open shower mixer valve/system outlets to maximum hot and cold to check the natural flow 

(unpumped) MUST be at least 1 litre in 30 seconds per side and 2 litres in 30 seconds mixed.

•  Open hot water outlets fully for 5 to 6 seconds and then turn outlets off. Then open cold 

water outlets fully for 5 to 6 seconds and turn outlets off. If flow is poor and inconsistent 

repeat above steps until flow is steady.

•  Repeat 2-3 times

The hot connection must be via an 

approved side or top entry flange

MAX

60°C

Outlet

Outlet

Inlet

Inlet

Содержание CT Force Series

Страница 1: ...Pump installation and warranty guide for the CT range of pumps CT FORCE CT Xtra and CT Bathroom Models shown CT FORCE 15PT CT 50 Xtra CT 60BU Bathroom ISSUE E JAN 2017 Quality Technology Service Value...

Страница 2: ...you first rate advice regarding installation Consulting the helpline at the time of installation may entitle your customer to an additional 1 year FREE warranty cover UK Only for CT Xtra CT Bathroom...

Страница 3: ...ct description 4 Installation instructions 4 Step 1 Pump location 6 Step 2 Connecting the pump 10 Step 3 Electrical installation 11 PumpWise Guidelines 12 General specifications 17 Technical specifica...

Страница 4: ...ern to the cold water mains inlet Multiple cold water storage cisterns must be linked in accordance with current plumbing regulations and the bottom of the cisterns must be at the same level Hot water...

Страница 5: ...ature stated in the installation guide Never use mechanical tools to tighten plastic coupler nuts as this may cause damage and invalidate your warranty Never use jointing compounds Boss White Hemp or...

Страница 6: ...RCE 20 IPT 30 IPT CT Bathroom 60B 80B and CT Xtra 64H 69H 84H 94H are whole house pumps CT FORCE 15 TU 15 ITU 20 TU 20 ITU 20 SU 20 ISU 30 TU 30 ITU 30 SU 30 ISU CT Bathroom 60BU 80BU 90BU and CT Xtra...

Страница 7: ...sed A Salamander S flange or one of the 22mm approved top entry flanges see page 14 22mm No Stop Essex flange with 76mm dip pipe and birds beak cut end to limit air being drawn into the pump Indirect...

Страница 8: ...should be installed in accordance with BS7671 2008 it should also be noted that BS7671 2008 is a guide In BS7671 2008 rooms containing baths or showers should be broken down into zones These zones ar...

Страница 9: ...entry flange is fitted 13 If pump is fitted above cylinder a No Stop Essex flange must be used 14 Check that water storage capacity recovery meets required flow rates particularly at peak demand i e a...

Страница 10: ...uired Salamander s universal range of pumps activate the pump automatically even where no natural flow exists UK CT pumps suitable for negative head operation are CT FORCE 15 TU 20 TU 20 SU 30 TU and...

Страница 11: ...ng valves are open Fill system Check for leaks DO NOT RUN PUMP DRY to do so will cause irreparable damage to your pump and will invalidate your warranty Open shower mixer valve system outlets to maxim...

Страница 12: ...arter turn Mechanical tools must not be used to tighten plastic coupler nuts as this may cause damage which will invalidate the warranty B Hose to pump Do not twist or bend anti vibration hoses as thi...

Страница 13: ...facturer it s service agent or similarly qualified person in order to avoid a hazard All pipe work must be cross bonded in accordance with the IET Regulations The pump is supplied with a fuse fitted H...

Страница 14: ...to meet the increased demand of a pumped system a water starvation protection unit WSP may be considered See fig 11 The WSP is a Salamander level switch which must be positioned 102mm higher than the...

Страница 15: ...sal pump Horizontal cylinders As horizontal Torpedo cylinders are problematic for boosted systems consult PumpWise on 0191 516 2002 for guidance and correct use of an approved top entry flange S flang...

Страница 16: ...or two or more bathrooms the cold feed to the cylinder MUST be in 28mm pipework Water hammer protection Water hammer most commonly occurs in systems where there are long pipe runs supplying solenoid a...

Страница 17: ...mperature of the stored water should not normally exceed 60 C and in a combined central heating and domestic hot water system it is recommended that the stored water temperature is controlled independ...

Страница 18: ...ooster pumps in systems where the temperature of the stored hot water is uncontrolled see below Usable capacity minimum 50 galls per bathroom Vent and other services Salamander approved HWS TMV Blendi...

Страница 19: ...water supplies can cause the mechanical seal to stick if left for long periods without use The pump must be run at least five minutes every four weeks to exercise all working parts Connections BSP mal...

Страница 20: ...pplies can cause the mechanical seal to stick if left for long periods without use The pump must be run for at least five minutes every four weeks to exercise all working parts Connections BSP male In...

Страница 21: ...215 205 FORCE 20 PS FORCE 20 IPS 2 0 Bar Single End Positive Head Shower Pump 3 3A 3 130 1 3 170 1 7 200 2 0 22mm 21mm 3 4 22 190 120 165 5 27 295 215 205 FORCE 30 PS FORCE 30 IPS 3 0 Bar Single End P...

Страница 22: ...m 5 3 78 195 120 165 4 55 295 215 205 CT 75 Xtra 2 0 Bar Twin End Positive Head Shower Pump 3 3A 3 150 1 5 170 1 7 200 2 0 15mm 3 Inlet only 3 78 195 120 165 4 55 295 215 205 CT 79 Xtra 2 0 Bar Twin E...

Страница 23: ...Pump 3 3A 3 140 1 4 160 1 6 180 1 8 21mm 3 3 38 195 120 165 4 10 295 215 205 CT 94 H Xtra 2 6 Bar Single End House Pump 3A 200 2 0 240 2 4 260 2 6 21mm 5 22 225 120 165 6 06 295 215 205 CT Xtra CT Bat...

Страница 24: ...flow Ensure that all AV couplers are straight and not bent or distorted Air in system Run system on full hot with pump switched off i e gravity only for several minutes Check cold water storage is co...

Страница 25: ...e helpline 0191 516 2002 PumpWise from Salamander helps customers and provides a support service second to none Installers and customers can be sure of a speedy response to requests for technical help...

Страница 26: ...ng sensation brought to you by your Salamander Pump complete and return the attached Warranty card within 15 days of purchase take care that the temperature of your stored water NEVER exceeds the reco...

Страница 27: ...aced by a type not specified by the Company or if the equipment is incorrectly installed operated or used other than as described in the instruction manual or if any servicing or repair of the equipme...

Страница 28: ...ided the warranty card is completed and returned to the Company within 15 days of purchase iv Where the PumpWise helpline has been contacted and the recommendations implemented the warranty periods de...

Страница 29: ...le for equipment purchased and used exclusively in the UK and The Republic of Ireland only g Where the Company issues a replacement the equipment replaced shall be returned to the Company forthwith an...

Страница 30: ...28 Notes...

Страница 31: ...Freepost RLXE JHHY HLHJ Salamander Pumps Unit 2c Colima Avenue Sunderland SR5 3XE...

Страница 32: ...e hot water 8 Does the hot water cylinder have a flange fitted Yes n no n Surrey n Warix n No Stop Essex n 1st Tee on downward leg n 45 vent n 9 What size is the supply pipework to the pump 15mm n 22m...

Отзывы: