Light Commercial R410A on-off
S13-01.01.13en
3.
Additional Refrigerant Charge
Caution
● Refrigerant cannot be charged until field wiring has been completed.
● Refrigerant may only be charged after performing the leak test and the vacuum pumping.
● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.
● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that
the appropriate refrigerant is charged.
● Refrigerant containers shall be opened slowly.
● Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added
diameter and the length of the liquid side pipe of the outdoor unit/indoor unit
refrigerant according to the
Remark:
R (g): Additional refrigerant to be charged
L (m): The length of the refrigerant pipe (one-way)
D (mm): Liquid side piping diameter
Installation
110
R(g) D(mm)
L(m)
φ6.4
Φ9.5
Φ12.7
Less than 5m (One-way)
—
—
—
Added Refrigerant When
Over 5m(One-way)
11g/m
×(L-5)
30g/m
×(L-5)
60g/m
×(L-5)
Содержание SIB-100BAY
Страница 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013 ...
Страница 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5 ...
Страница 14: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Four way Cassette Type Compact 13 ...
Страница 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47 ...
Страница 55: ...Light Commercial R410A on off S13 01 01 13en SIB 100TAY SIB 140TAY SIB 200TAY Indoor Units Ceiling Floor 54 ...
Страница 62: ...Light Commercial R410A on off S13 01 01 13en SIB 50TAV SIB 60TAV Indoor Units Ceiling Floor 61 ...
Страница 63: ...Light Commercial R410A on off S13 01 01 13en SIB 100TAY SIB 140TAY SIB 200TAY Indoor Units Ceiling Floor 62 ...
Страница 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67 ...
Страница 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68 ...
Страница 72: ...Light Commercial R410A on off S13 01 01 13en 5 3 SIB 140DAY SIB 200DAY Indoor Units HSP Duct Type 71 ...
Страница 81: ...Light Commercial R410A on off S13 01 01 13en 11 Field Wiring SIB 60DAV Indoor Units HSP Duct Type 80 ...
Страница 82: ...Light Commercial R410A on off S13 01 01 13en SIB 100DAY SIB 140DAY SIB 200DAY Indoor Units HSP Duct Type 81 ...
Страница 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90 ...
Страница 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91 ...
Страница 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92 ...
Страница 117: ...Light Commercial R410A on off S13 01 01 13en 6 Wiring Please refer to the Wiring Diagram Installation 117 ...