Parameter
Name
Setting Range
Default
Property
Address
zone
F6.06
User-defined output
comparison value 1
0
~
65535
0
○
0606
F6.07
User-defined output
comparison value 2
0
~
65535
0
○
0607
F6.08
AO1 Output Option
0
:
Running Frequency
(
0
~
F0.05
)
1
:
Set Frequency
(
0
~
F0.05
)
2
:
Output Current
(
0
~
Double Rated
Current of VFD
)
3
:
Output Voltage
(
0
~
1.2times of VFD
Rated Output Voltage
)
4
:
AI
(
0
~
10V
)
5
:
Bus Voltage
(
0
~
500.0/1000.0V
)
0
○
0608
F6.09
AO2 Output Option
0
○
0609
F6.10
AO1 offset coefficient
-100.0%
~
+100.0%
0.0%
○
060A
F6.11
AO1 gain
-10.00
~
+10.00
1.00
○
060B
F6.12
AO2 offset coefficient
-100.0%
~
+100.0%
0.0%
○
060C
F6.13
AO2 offset coefficient
-10.00
~
+10.00
1.00
○
060D
F7.00
Reserved
Reserved
0
○
0700
F7.01
STOP Button Function
0
:
Valid only at keypad control mode
1
:
Valid at all control modes
1
○
0701
F7.02
LED display parameters at
running status
Bit0
:
Running Frequency(Hz)
Bit1
:
Set Frequency(Hz)
Bit2
:
Bus Voltage(V)
Bit3
:
Output Voltage(V)
Bit4
:
Output Current(A)
Bit5
:
DI Input Status
Bit6
:
DO Output Status
Bit7
:
Keypad Knob Voltage(V)
Bit8
:
AIVoltage(V)
Bit9
:
Load Speed
Bit10
:
PID Set Value
Bit11
:
PID Feedback Value
Bit12
:
PLC Stage
Bit13
:
Feedback Frequency
(
Unit
:
0.1Hz)
Bit14
:
Communication Set Value
Bit15
:
Main Frequency Source X
0x1F
○
0702
F7.03
LED display parameters at
stop status
0x06
○
0703
F7.04
Load
speed
display
coefficient
0.0001
~
6.5000
3.000
○
0704
F7.05
Software Version
-
-
◎
0705
F8.00
Jog Running Frequency
0.00Hz
~
F0.05
2.00Hz
○
0800
F8.01
Jog Acceleration Time
0.0s
~
100.0s
10.0s
○
0801