SAH WSK Series Скачать руководство пользователя страница 7

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER

The host query:

Query message frames includes device address, function code, data, information, check code. Address 
code informs the machine that is selected to perform the destined function equipment, such as functional 
code 3 or 4 is for registering the data which is read from the device and return their content; Contains data
from the device to perform functions other additional information, such as reading command, data
segment additional information start from how to register and number of registers to read; Check code is
 used to test the correctness of the a frame information, provides from the device with a validation 
message content is the right approach, it adopts CRC16 calibration rule

If from the device to produce a normal response, in response to the message from the machine address 
code, function code, code and data information CRC16 check code. Data information code, including the
 data collected from the device, such as register values or state. If there are errors, we agreed from the 
machine does not respond. Transport refers to a data frame in a series of separate data structure and used 
for the transmission of data limited rules, defines the RTU mode compatible with MODBUS agreement 
under the mode of transmission. Each byte: a start bit, 8 data bits, parity bit (,), 1 stop bit (a parity bit) or 
1 stop bit (and white parity bits).

The structure of the data frame:(Message format) Table 1

Address Code

Address Code

Function Code

Data Code

Check Code

Table

At the beginning of a frame by a byte (eight binary code), the decimal is 0-255, only use the 1-247 in our 
system, the other address. These bits indicate the address specified by the user terminal equipment, the 
device will accept data from the connected to the host. Each terminal equipment address must be unique, 
only by addressing to the terminal response contains the address of the query. When the terminal sends 
back a response, in the response from the machine address data and tell the host which terminal is to 
communicate with them.

ONE

ONE

ONE

ONE

TWO

TWO

CODE

Meaning

Behavior

Function Code: (Table 2)

Tell what is addressing to the terminal to perform the function. Listed in the following table shows the 
supported code function, and their meaning and function

Table

Query data frame 

(

main

 

machine

)  ( 

Table 3

)

Table

Table

Table

Table

Address

Address

Address

Address

Command

Command

Command

Command

The starting
    register 
    address 
      (high)

The starting
    register 
    address 
      (high)

The starting
    register 
    address 
      (high)

The starting
    register 
    address 
      (high)

The starting
    register 
    address 
      (low)

The starting
    register 
    address 
      (low)

The starting
    register 
    address 
      (low)

The starting
    register 
    address 
      (low)

Quantity of 
    register
    (high)

Quantity of 
    register
    (high)

Quantity of 
    register
    (high)

Quantity of 
    register
    (high)

Quantity of 
    register
    (low)

Quantity of 
    register
    (low)

Quantity of 
    register
    (low)

Quantity of 
    register
    (low)

low

low

low

low

high

high

high

high

 Record 
the data

Response data (from the machine frame), indicating that the data has been written. (table 6)

Query data frame (the host machine) (see table 5)

The response data (from the machine frame) (see table 4)

     This function allows the user to change the contents of a register, is written to the data to be
 highlighted as writable attribute, the number of address range is not more than, this example  
is written communication

Check code

:

     Error check (CRC) domain are two bytes, containing a 16-bit binary values. CRC value is calculated 
by the transport equipment, and then attached to a data frame, the receiving device to recalculate the CRC
 value when receiving data, and then compared with acceptance to the CRC in the domain of value, if the
 two values are not equal, an error has occurred. As shown in figure 3

         Read data (functional code: 3) : this function can users get the terminal equipment acquisition \ 
     recorded data, as well as the system parameters. Host a request there is no limit to the number of data 
     collected, but not beyond the definition of address range

Communication message example

Содержание WSK Series

Страница 1: ...WSK INTELLIGENT TEMPERATUREAND HUMIDITY CONTROLLER USER MANUAL ...

Страница 2: ...n to prevent the power cord and input output strong current shock 2 Power supply In order to prevent the equipment damage or failure please use the rated power To prevent electric shock or equipment failure all wiring complete rear can supply 3 Prohibited to use in the vicinity of flammable gas As fire explosion or equipment damage banned in flammable explosive gas venting occasion use 4 It is for...

Страница 3: ...er supply 85V 265V 50 60Hz AC Transformer 110V 220V 380V 50 60Hz DC 24V 36V 48V 110V 220V Accuracy class Temperature 0 5 C Humidity 5 RH Resolving power 14 Bit Cycle of sampling 0 5 Sec Measurement range Temperature 40 100 C Humidity 0 100 RH Display Measured values and set values by LED Output condition and alarming condition by LED lights Way of operating Controlling by two step settable turn di...

Страница 4: ... TEMPERATU RE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATU RE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATU RE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER The wiring diagram subject to the product itself the wiring diagram 485 Frame Size Hole Size Frame Size and Hole Size Frame Size and Installation Hole S...

Страница 5: ...indicator lights The communications light Instrument power light work Increasing Key Decreasing Key Up Key Down Key Displacement Key Mode Key Confirm Key Quit Key Operation Process Boot Up Process Open the Power Self checking of LED device Automatic Automatic Transfomation Transfomation Displaying the current temperature and humidity All LEDS light up Measuring the current temperature and humidity...

Страница 6: ...s the master slave communication response mode connections on a communication line First of all the main computer of the signal only address addressing to a terminal equipment machine and then the response signal from the terminal to transmit to host in the opposite direction i e in a single communication line signal transmission instead of two direction all communication data flow half duplex wor...

Страница 7: ...he address of the query When the terminal sends back a response in the response from the machine address data and tell the host which terminal is to communicate with them ONE ONE ONE ONE TWO TWO CODE Meaning Behavior Function Code Table 2 Tell what is addressing to the terminal to perform the function Listed in the following table shows the supported code function and their meaning and function Ta...

Страница 8: ...ng setting Temperature heater disconnection alarming setting Temperature process alarming setting Humidity process alarming setting Humidity process alarming state Temperature process alarming state ON ON ON ON OFF OFF OFF OFF OFF Lower deviation alarming Lower deviation alarming Higher deviation alarming Higher deviation alarming 3 is the highest brightness the lED display brightness the controll...

Отзывы: