Saginomiya type ule Скачать руководство пользователя страница 4

(Temperature Display Value Compensation Function)

Calibration can be performed by pressing [UP] key and [DOWN] key with in the range of

±5℃ referring to the value of the present temperature when Calibration mode was

selected.

Type ULE turns into Calibration mode by pressing [UP] key and [DOWN] key simultaneously

normal operation mode, and the preset temperature will be displayed.

for about 8 seconds.If no keys are pressed for about 10 seconds, the device turns into

How to perform Calibration

The device is in normal operation, and the present
temperature is displayed.

Pressing none

<Setting sequence>

[CAL] offset, [Present temperature], and [CAL]

letters will be displayed on and off one after

the other. [CAL] offset, [Present temperature],

and [CAL] letters will be displayed on and off

one after the other, and [CAL] offset can be

changed.

pressing [UP] key and [DOWN] key
simultaneously for about 8 seconds

[[CAL] value change]

7.Calibration Function

Unless otherwise agreed by the parties,warranty period of the product shall be one
year after date of delivery to Buyer.
In case of failure attributable to the Company within such period,the product shall

① Improper handling or application by user.
② Modification or repair by other than the Company.

Warranty described in this paragraph means the warranty for the Product itself and
dose not include warranty for any consequential damage arising out of or occasioned

by a defect or failure of the Product.

③ Any failure to be caused by acts of God,fire,storm or the like,war,riot or the

be repaired or replaced without charge,provided that any one of followings are out
of the warranty:

like and other causes beyond the control of the Company.

13.Scope of Warranty

[CAL] offset change by 0.5℃, and by 1℃ if

the temperature is 100℃ and higher.

Pressing [UP]
or[DOWN] key

!

CAUTION

●Key operations should be done while the present temperature is displayed.

●Make sure that calibration is performed accurately using the standard thermometer

when the temperature to be measured is stable and without fluctuations.

Calibration should be performed referring to the value of the preset temperature

when Calibration mode was selected

●The value during calibration will become the present temperature and the device

will operate referring to it.

Depending on the preset [ON] and [OFF] values, the

control power output could be switched on or off during calibration.

preset temperature values that are not calibrated.

●There may be greater disagreement between the real temperature values and the

Failure in observing the following could result in injuries

The device turns into normal operation, and the present

temperature will be displayed, if no keys are pressed for

about 10 seconds.

Pressing none

of operators, or damage and malfunction of the device.

12.Check Points on Trouble

Causes

Phenomenon

All of digital indications disappear.

Digital indication displays“Lo”.

Digital indication displays“Hi”.

Digital indication displays“Err”.

・Power failure.

・Power is not supplied.

temp. of indication range.

・The detected temp. is lower than minimum

・Sensor is disconnected.
・Sensor lead broke.

・The detected temp. is higher than maximum

temp. of indication range.

・Sensor short-circuited.

・Failure of set point.
・Turn OFF the power once and turn ON the

power again.

・In case continues Err indication, it means

out of order of the Product.

・As the temp. indication flashes, reset

the each temp. set point.

Digital indication displays "888".

・When apply the power to the ULE, display

everytime.

Tokyo 165-8907 Japan

E-mail:inter@saginomiya.co.jp
URL:http://www.saginomiya.co.jp

55-5、Wakamiya 2 chome,Nakano-ku,

Tel:+81 3 3330-8161

Fax:+81 3 3330-8175

Continuance of control output ON
or control output OFF

than “ON” set point.

・On cooling Mode:“OFF”set point is higher

・On heating Mode:“OFF”set point is lower

than “ON” set point.