background image

11.How to Setup

1.Operation

1)Cooling mode(2 step)

The following method can change ON-OFF set values of thermostat No.1 and No.2.

(initializing for factory preset mode or shaking down, for example).

Follow the instruction below when construction contractors setup the all values

Pressing none

<Setting sequence>

Pressing [SEL] key

The device is in normal operation, and the present temperature
is displayed.

Pressing [SEL] key

Pressing [SEL] key

Pressing [SEL] key

[Setting the values for [OFF1]]

When [oFF1] and [OFF1-value] blinks alternately,
and the orange LED at the [OFF1} position,the
value for the [OFF1-value] setting can be changed.

[Setting the value for[ON1]]

Change [OFF1-value] by 0.5℃.

When the set value of OFF1 is changed,the set
value ON1 remains unchanged.

When [on1] and [ON1-value] blinks alternately,
and the orange LED at the [ON1] position, the
value for the [ON1-value] setting can be changed.

[Setting the values for [OFF2]]

When [oFF2] and [OFF2-value] blinks alternately,
and the orange LED at the [OFF2] position, the
value for the [OFF2-value] setting can be changed.

[Setting the value for[ON2]]

Change [OFF2-value] by 0.5℃.

When the set value of OFF2 is changed,the set
value ON2 remains unchanged.

When [on2] and [ON2-value] blinks alternately,
and the orange LED at the [ON2] position, the
value for the [ON2-value] setting can be changed.

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

Off

On

(set value)

temperature

min.0.5℃

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

(set value)

temperature

Off

On

min.0.5℃

2)Heating mode(2 step)

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

(set value)

temperature

min.0.5℃

On

Off

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

(set value)

temperature

min0.5℃

On

Off

3)Floating mode

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

(set value)

temperature

min.0.5℃

On

Off

On

Off

or

control output 1
⑥-⑦ terminal

control output 2
⑧-⑨ terminal

(set value)

temperature

Off

On

min0.5℃

In Cooling Mode, when the current temperature drops below the set value of OFF, the

relay circuit turns off, and turns on when the current temperature rises higher than

In Heating Mode, when the current temperature drops below the set value of ON, the

relay circuit turns on, and turns off when the current temperature rises higher than

When the set value of ON is changed, the set value of OFF remains unchanged.

When the set value of OFF is changed, the set value of ON remains unchanged.

3.Example of changeing [OFF1] and [ON1] setting.

Following is the example of changing from [OFF1] and [ON1] set values 0℃ and 2℃,

7.Press [SEL]key shift through each setting for confirming.
8.Press[ENT]key to replase each setting value and then return to normal operation.

4.Press[▼] key change from [2.0]℃→[2.5]℃→・・・[4.5]℃→[5.0]℃.

2.Press[▲]key change from [0.0]℃→[0.5]℃→・・・[9.5]℃→[10.0]℃.

[OFF2] and [ON2] set values 1℃ and 3℃ to [OFF1]and[ON1]set values 10℃ and 5℃,

[OFF2] and [ON2] set values 1℃ and 3℃.

7SEG.. LED. The set value of [OFF1-value] means [off1]value of 0℃.

1.Press[SEL]key to confirm that[oF1]and[OFF1-value]are blinking alternately at

7SEG.. LED. The set value of [ON1-value] means [on1]value of 2℃.

3.Press[SEL]key to confirm that[on1]and[ON1-value]are blinking alternately at

7SEG.. LED. The set value of [OFF2-value] means [off2]value of 1℃.

5.Press[SEL]key to confirm that[oF2]and[OFF2-value]are blinking alternately at

7SEG.. LED. The set value of [ON2-value] means [on2]value of 3℃.

6.Press[SEL]key to confirm that[on2]and[ON2-value]are blinking alternately at

Type ULE can lock keys to prevent wrong operations by pressing [UP] key and [ENT]

key simultaneously for five seconds. While the key locking function is actuated,

Setting Change mode cannot be selected by pressing [SEL] key. Only [Loc] is displayed

on and off. No other modes can be selected either by pressing other keys. Only [Loc]

is displayed on and off. The device will operate at preset values of [ON] and [OFF]

while Keylock function is actuated.

4.Keylock Function

Press [UP] key and [ENT] key simultaneously for five seconds.

How to lock keys

Press [UP] key and [ENT] key simultaneously for five seconds. [Loc] will be displayed on
and off. Keep pressing those keys. When the preset temperature is displayed, keylock

Function is canceled.

How to cancel Keylock function

!

CAUTION

Failure in observing the following could result in injuries

●When the device resets itself after an electric power failure, keylock Function

is canceled and should be actuated again.

●Key operations should be done while the present temperature is displayed.

of operators, or damage and malfunction of the device.

the set value of ON.

the set value of OFF.

!

of operators, or damage and malfunction of the device.

Failure in observing the following could result in injuries

CAUTION

unnecessarily small. It may shorten the life span of the thermostat.

●The minimum value difference between [ON] and [OFF] is 0.5℃. Do not make the [DIFF]

●Be sure to check the each setting point and press [ENT] key to replace each setting

value and then return to normal operation.

And two thermostat function is set the each point regardless the mutual set points.

An each function of the two-step, the floating and the limit can be carried out by

a combination of settings. In case of cooling mode, the temp. setting point of OFF

should be lower than that of ON. In case of heating mode, the temp. setting point of

OFF should be higher than that of ON.

When the set value of ON1 is changed,the set
value OFF1 remains unchanged.

Change [ON1-value] by 0.5℃.

Pressing [UP]
or[DOWN] key

Pressing [UP]
or[DOWN] key

Pressing [UP]
or[DOWN] key

Pressing [UP]
or[DOWN] key

Pressing the [ENT] key

[Returns to the current temperature mode]

Change [ON2-value] by 0.5℃.

When the set value of ON2 is changed,the set
value OFF2 remains unchanged.

Durning setting, from any mode, returning to normal operation is
possible after replacing values in memory. Existing values remain
valid until [ENT(Enter)] key is pressed, and normal operation
continues. Each set value remains protected even when the power
is disrupted. When the power is disrupted within one second after

returning to normal operation, the memory may be lost.

2.Change ON-OFF set value

blink

OFF

ON

SET 1

blink

OFF

ON

SET 1

blink

OFF

ON

SET 2

blink

OFF

ON

SET 2

Отзывы: