IMPORTANT:
These setting are necessary in order to avoid
rendering the Evolion
®
unusable and requiring a site intervention.
#
Type
Value
a.
Single level charge voltage
56.0 V ± 0.5% (all charge
operations)
(Note 1)
b.
Temp. Comp. V. (TCV)
Turned OFF or Disabled
c.
Max. re-charge current
See Table 6
d.
Ramp in voltage
Longest setting up to
3 minutes
e.
Default rectifier voltage
42 V to 46 V
f.
Low Voltage Disconnect
45 V (≤ 12 in parallel)
46 V (> 12 in parallel)
Duty
Max. per
Evolion
®
(Note 1)
To avoid
overheating
4x cycles per day or more
16 A
3x to 4x cycles per day
21 A
2x to 3x cycles per day
24 A
1x to 2x cycles per day
32 A
To avoid charge
regulated mode
1x cycle per day or less
21 A
Figure 9. Connecting Communication to the Application
Figure 9 Steps
(refer to illustration and tools)
1
Prepare a communication cable to connect to the application.
2
Color match the pins according to 568A or 568B cable.
3
Connect the prepared cable ends to the application.
The Evolion
®
is now ready for communication and Figure 10.
Table 5. Rectifier settings
Note 1: The Evolion
®
operates normally between 49.5 V to 56.0 V. The
highest %SOC is reduced by 10% for each 1 V below 56.0 V.
Figure 10. Powering ON
Figure 11 Steps
(refer to illustration and tools)
CAUTION:
Make sure the Evolion
®
is OFF and disconnected
before conducting these steps.
1
Remove the front cover.
2
Remove the fuse cover.
3
Check the fuse continuity (close to zero ohms = good fuse);
replace fuse (781081) as necessary. Replace fuse cover
4
Turn ON the Evolion
®
5
Check LED state (Table 3) and push BMST reset button
as necessary to clear alarms.
6
Turn OFF the Evolion
®
.
The Evolion
®
is now ready for storage or service.
Figure 10 Steps
(refer to illustration and tools)
Make sure the AC power is ON and the rectifier controller is
operating normally.
Make sure the Evolion
®
modules are turned OFF.
1
Turn ON the rectifier output power. The Evolion
®
modules
will automatically wake up and begin charging after a few
seconds.
2
Observe the LED’s (see Table 3).
The Evolion
®
is now in service.
Table 6. Maximum Re-charge Current Settings
Saft
Industrial Battery Group
12, rue Sadi Carnot
93170 Bagnolet - France
Tel : +33 (0)1 49 93 19 18
Fax: +33 (0)1 49 93 19 64
www.saftbatteries.com
Doc. Nº 21952-0516-2
Edition: May 2016
Data in this document is subject to change without
notice and becomes contractual only after written
confirmation.