![Saft evolion Скачать руководство пользователя страница 2](http://html2.mh-extra.com/html/saft/evolion/evolion_installation-and-operation-instruction-sheet_3398618002.webp)
Pin
Type
1
RS485+
2
RS485-
3
Ground (isolated from power
terminals)
4
Wake up (+12 V to ground)
5
Not used
6
Not used
7
Dry contact alarm loop
8
Dry contact alarm loop
Table 1. Included with the Evolion
®
kit, 782674 (-11)
Table 2. SOC/SOH LED legend (after pushing button)
Table 3. Operating LED legend (no push button)
P/N
Description
Qty
Illustration
782672-
XX
(Note 1)
Evolion
®
3.9 kWh
module
1
781081
Fuse, replaceable,
spare
1
772516
(Note 2)
Power cable, 8
GA., ¼” ring lugs,
positive, 1 meter
1
772517
(Note 2)
Power cable, 8
GA., ¼” ring lugs,
negative, 1 meter
1
772518
Comm. cable, RJ45
male (x2), 1 meter
1
773455
Resistor cap, RJ45
male
1
#
LED state
SOC
(Push < 3 sec.)
(LED’s steady)
SOH
(Push ≥ 3 sec.)
(LED’s flashing)
1
< 25% SOC
charge is
necessary
< 25% SOH
< 77% Ah
avail.
2
≥ 25% SOC
Store
(7 months)
or operate
≥ 25% SOH
≥ 77% Ah
avail.
3
≥ 50% SOC
Store
(13 months)
or operate
≥ 50% SOH
≥ 85% Ah
avail.
4
≥ 75% SOC
Store
(20 months)
or operate
≥ 75% SOH
≥ 92% Ah
avail.
#
LED state
Description
A
Floating or Forbidden Charge
Mode (warning alarm #11)
B
Charging in fast charge mode
or regulated charge mode
C
Discharging
D
Warning alarm
(continues normal operation),
See 9. Troubleshooting
E
Major alarm (disconnected),
See 9. Troubleshooting
F
Bootloader mode
(only when used with
Evolion
®
Toolbox Software)
G
Sleep or OFF
Note 1: The kit variant is indicated by the”-
XX
”. The standard kit is
shown in Table 1 is the
-11
variant.
Note 2: The power cable assembly and part number may vary based on
the kit variant.
Figure 1. Lifting
Figure 3. Evolion
®
features
1
Only use the lifting points.
NOTE:
The Evolion
®
weighs 30 kg (66 lbs).
IMPORTANT:
Using other than the lifting points shown may
cause irreparable damage.
1
ON/OFF push button, 2 seconds ON – 4 seconds OFF
2
SOC (State of Charge) and SOH (State of Health) push
button, see Table 2
3
LED1 (left), LED2, LED3 and LED4 (right), see Table 2
and 3
4
Positive power terminal, M6 hex head bolt
5
Negative power terminal, M6 hex head bolt
6
Grounding point, M3 socket head screw
7
Front cover, 3.5 mm x 12 mm, self threading, torx head
screw
8
BMST micro-processor reset button
9
Replaceable fuse (not shown) and cover, use only 771285
RJ45 (female) – 2 jacks with pins connected in parallel
Note 1: To diagnose the alarms, use the Evolion
®
Toolbox Software
available in the Evolion
®
Communication Kit (772309)
(Note 1)
(Note 1)
10