42
n°
Fault code is active (major alarm) with open electronic switch (mosfet); Evolion operates in safe mode.
n°
Warning alarm is active with closed electronic switch; Evolion operates in normal mode.
Generic
n°
Buffer
n°
Description
Fault condition
Possible cause and notes
Recommended action guide
60
36
Unbalanced cells
[NewSocMaxCalculate
= 1 (soc refreshed)]
AND [minimum SOC
> 25 %] AND [cell
voltage difference
> 100 mV] AND
[minimum cell voltage
> 3.5 V for 2 s]
• Internal fault detection
function
• Possible faulty BMST busbar
board
1. Continue float operation for
1 or a few days (depends on
level of imbalance).
2. Voltage must be above 3.5 V
per cell to have balancing
circuits active.
3. Temperature of the module
must be lower than 55 °C for
balancing circuits to be active.
4. Alarm will be reset
automatically after the cell
voltage difference is within
allowed limit.
5. If fault persists, contact your
local Saft representative.
68
37
IMD/IMR from
algorithm are invalid
If the IMD/IMR
calculation function
is in error state and
reinitialization failed
• Software issue
1. Contact your local Saft
representative if it persists.
70
38
Outputs from the
AlgoSaftGetPowerPred
function are invalid
If the Power
Prediction calculation
function is in error
state
• Software issue
1. Contact your local Saft
representative if it persists.
71
0
Microprocessor cycle
overtaking or cycle
error
Software cycle
duration is greater
than expected
duration (according
to the mode)
• Software issue
1. Contact your local Saft
representative if it persists.
Appendix F: BMST versions
USB Key P/N
BMST software
version
Evolion P/N
DiagWinBMS
software
Bootloader HMI
RS485/USB
converter
772520-01
V0.51
771492-01
V1.16
N/A
Brainboxes
772520-04
V0.54B
771492-04B
V1.19C
N/A
Brainboxes
772520-05
V0.55
771492-05
V1.19F
V1.13
FTDI
772520-06
V0.56
771492-06
V1.19F
V1.13
FTDI
772520-07
V0.57
771492-07
V1.19H
V1.13
FTDI
772520-08
V0.58
771492-08
V1.19H
V1.13
FTDI
772520-09
V0.59
771492-09
V 2.9
V.1.17
FTDI
77520-09
(latest- REV)
V1.00
771492-09 **
Evolion
Toolbox software
V1.17
FTDI
** - variable indicates parameter file version