The Evolion automatically protects against abusive operation.
There are two basic approaches to size the Evolion. For autonomy sizing or frequent cycling sizing contact your local Saft
representative for further assistance.
14. Abusive operations
15. Battery sizing
Abusive operation
Protection description
Reverse connection to power terminals
The Evolion will not start if there is a reverse connection. It will
remain in sleep mode. If the ON/OFF button is forced ON, then the
Evolion will wake up in safe mode with Alarm 27 and 47.
External short circuit
Replaceable fuse will act.
Temperature, voltage or current outside of acceptable range
See chapter safety limits during operation and Appendix E Alarms
and troubleshooting.
Connecting Evolion in series
Never install Evolion batteries in any series connections. Failure to
follow these safety precautions may lead to irreversible damage
of internal electronics and failure of built in safety features. If
inadvertent series connects are noticed immediately disconnect
batteries and run DiagWinBMS software to check health status of
module.
Sizing method
Typical applications
Autonomy sizing
Telecom backup good grid and poor grid, photovoltaic
Frequent cycling
Consult with your local Saft representative for life and thermal
optimization.
15.1 Autonomy sizing
To determine the # of Evolion modules needed to provide a minimum autonomy, use the following equation along with the performance
rate tables and external derating factors. See the chapter Discharge performance factors and the rate table and graphs in Appendix C
and D for more details.