38
n°
Fault code is active (major alarm) with open electronic switch (mosfet); Evolion operates in safe mode.
n°
Warning alarm is active with closed electronic switch; Evolion operates in normal mode.
Generic
n°
Buffer
n°
Description
Fault condition
Possible cause and notes
Recommended action guide
12
9
A cell is going under
voltage
Cell voltage < 2,55 V
during 2 s
• Too long period of rest after
complete discharge (42 V
cutoff) and before start charge
• ON/OFF button left ON in long
storage
• Too high cell self-discharge
• Too high cell dispersion at end
of complete discharge
• Refer to alarm 60
• At 2.5 V, IMD_C will be zero
and as a result the electronic
switch will open in safe mode.
• Refer to alarm 24
• At 3.0 V, the module will go into
sleep mode automatically after
1 hour.
1. This alarm is active normally
in storage or when not
connected in operation or at
the end of discharge.
2. Begin refreshing charge
procedure immediately
3. Evolion auto resets after
correction of cause and fault
condition.
4. Continue operation without
fault.
5. If fault persists, contact your
local Saft representative.
13
10
A cell is under
voltage
Cell voltage < 2,15 V
during 2 s
• Redundant safety feature in
microprocessor
• Refer to alarm 12
1. This alarm is active normally
in storage or when not
connected in operation.
2. Begin refreshing charge
procedure immediately
3. Reset the module.
a. For single connected module,
turn output power from
rectifier OFF and then ON and
after the fault should reset.
b. For parallel connected
modules, BMST reset or
Evolion OFF/ON is necessary
4. Continue operation without
fault.
5. If fault persists, contact your
local Saft representative.
14
11
Mosfet temperature
out of range
If at least one mosfet
has a temperature
out of range during
1s (-40° C < T <
120 °C)
• Sensor failure short circuit or
open
• BMST power board may be
damaged
• Refer to alarm 40 and 41
1. Contact your local Saft
representative if it persists
15
12
Cell voltage out of
range
If at least one cell
has a voltage out of
range during 2s (1.5 V
< V < 4.5 V)
• Voltage measurement circuit
failure
• BMST busbar board may be
damaged
• Refer to alarm 10, 11, 12 and
13
• Refer to alarm 1
1. Contact your local Saft
representative if it persists.
16
13
Cell temperature out
of range
If at least one cell
has a temperature
out of range during
2 s (- 40 °C < T <
120 °C)
• Sensor failure short circuit or
open
• BMST busbar board may be
damaged
• Refer to alarm 6, 7, 8 or 9
• Refer to alarm 1
1. Contact your local Saft
representative if it persists.
19
14
High battery supply
BMST supply voltage
> 32 V during 0.5 s
• Internal fault check function
• Possible faulty BMST
electronics
1. Contact your local Saft
representative if it persists.
20
15
Battery 12 V supply
is low
BMST supply voltage
< 11.5 V during 0.5 s
• Internal fault check function
• Possible faulty BMST
electronics
1. Contact your local Saft
representative if it persists.