52
Recommended Renewal Parts and Replacement Procedures
01.4IB.77000B
PowlVac-ND® Vacuum Circuit Breaker
Table F Control Devices
Control
Voltage
Closing Coil
Assembly
Primary
Shunt
Trip Coil
Assembly
(3 cycle) (2)
Primary
Shunt
Trip Coil
Assembly
(5 cycle)
Secondary
Shunt
Trip Coil
Assembly
(1, 3)
Undervoltage
Device
Assembly
Charging
Motor
Assembly
Anti-Pump Relay
Assembly (5)
48VDC
77026G01P
77027G01P
50041G01P
50042G01P
(4)
77318G01P RR2BA-US-DC-48V
125VDC
77026G03P
77027G02P
50041G02P
50042G03P
(4)
77318G02P RR2BA-US-DC 110V
250VDC
77026G04P
77027G03P
50041G03P
50042G04P
(4)
77318G03P RR2BA-US-DC 110V
120VAC
77026G01P
77027G01P
50041G05P
50042G01P
n/a
77318G02P RR2BA-US-AC 120V
240VAC
77026G02P
77027G06P
50041G06P
50042G02P
n/a
77318G03P RR2BA-US-AC 240V
Capacitor
Trip (6)
n/a
50027G04P
50041G04P
50042G05P
n/a
n/a
n/a
Notes:
1) One required per circuit breaker if the circuit breaker was originally equipped with this item. All
circuit breakers have a closing coil, primary shunt trip coil, charging motor, and an anti-pump
relay assembly. Secondary shunt trip coils and undervoltage device assemblies are optional (see
notes 2-7).
2) Primary shunt trip coil is available as a 3 cycle and 5 cycle control device. A circuit breaker with an
original 5 cycle trip coil may not be replaced with a 3 cycle trip coil as damage to the circuit breaker
may occur. A circuit breaker with an original 3 cycle trip coil may be replaced with a 5 cycle trip
coil.
3) Secondary shunt trip coil cannot be furnished with an undervoltage device assembly.
4) Where furnished, cannot be present with secondary shunt trip coil assembly.
5) For 250VDC applications, a dropping resistor 50747G02P is required in series with the anti-pump
relay assembly.
6) For use with capacitor trip units with 240VAC input. Consult factory for other circuit breaker
ratings.
7) All control devices are available with push-on terminals. Consult factory for control devices with
screw terminals.