Installation
01.4IB.77000B
1) Removing the Circuit Breaker from the
Connected to the Test/Disconnected Position
a. Verify that the circuit breaker
open/closed indicator displays
“BREAKER OPEN”
and if not, operate
the circuit breaker control switch to
open the circuit breaker.
b. Place the racking handle socket onto
the racking drive shaft extension.
c. Turn the racking handle
counterclockwise until the breaker
position indicator displays
“TEST”
.
d. Remove the racking handle. This
is approximately 22 turns from the
“
CONN
” connected position.
Note:
This is the Test Position.
2) Removing the Circuit Breaker from the
Test/Disconnected Position out of the Circuit
Breaker Compartment
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure the
circuit breaker is in the open position and all
springs are discharged.
!
CAUTION
a. Open the circuit breaker compartment
door.
b. Lift the secondary disconnect latch
and remove the circuit breaker
compartment’s secondary disconnect
plug. Store the plug so it will not be
damaged while withdrawing the circuit
breaker.
Removal of the secondary disconnect plug will
trip a closed breaker and discharge the main
closing spring.
!
CAUTION
c. Press the anti-rollout latch downward to
release the circuit breaker and pull the
circuit breaker out of the circuit breaker
compartment (Figure 14).
Figure 14 Circuit Breaker Removal Applying
the Anti-Rollout Latch
a
a. Anti-Rollout Latch
3) Remote Racking
This is an alternative to the manual racking
procedures described above utilizing a
motor driven mechanism and electric
control, allowing the user to perform the
racking function without being located in
front of the circuit breaker compartment.
The Remote Racking Device
mounts onto
the compartment door when the circuit
breaker is racked with the compartment
door closed. Refer to the instruction
bulletin provided with the Remote
Racking Device for the proper operational
procedure.