Fault Finding Instructions SDS26
16.06.09
Seite 13 von 13
Problems with Fuses on Power Supply Module (SDS-2/6)
Blown
Fuse
Possible Reason
F1
Power supply module defective. Exchange power supply module.
F2
External short circuit on the bus cable. Please disconnect bus cable from
terminal nos. 17, 18, 19 and 20 at the power supply module and start
system again. If fuse does not break again, please examine the bus cable
to locate the short circuit.
F5, F6
Short circuit in fan unit no.1. Please disconnect cable for fan no.1 at
terminal nos. 5 and 6. and start system again. If fuse does not break again,
please examine the cable and fan motor no.1 to locate the short circuit.
F6, F7
Short circuit in fan unit no.2. Please disconnect cable for fan no.2 at
terminal nos. 7 and 8. and start system again. If fuse does not break again,
please examine the cable and fan motor no.1 to locate the short circuit.