background image

7

6

4. Installation and testing with Safera Siro 

and Siro R

1.  Connect all cables according to the pictures.

2.  Power up the system by connecting the power supply (the system should start 

normally).

3.  Press the OK-button on the Sensor Unit and check the color and amount of blinks 

on the light bars is correct according to these codes:

LED

Status

Remedy

One green 

blink

No Connection Hub detected.

Check the cables and 

system compatibility.

Two green 

blinks

Connection Hub is detected and 

working OK, but no CTU connection 

is present.

Three green 

blinks

Connection Hub is detected, and 

also a CTU is connected. Everything 

is working OK. If you remove the 

CTU after this, an error will be 

raised (two red blinks).

One violet 

blink

Problem with the communication 

between Sensor Unit and 

Connection Hub.

This will be raised if a 

Connection Hub is later 

removed from the system.

Two violet 

blinks

Connection Hub internal failure, for 

example component defect.

The Connection Hub is 

damaged and must be 

replaced.

Three violet 

blinks

Connection Hub has detected that 

the Power Supply of the Safera 

System is not working reliably or 

not providing enough power for a 

reliable extinguish launch.

The Power Supply must be 

replaced.

One red blink

The CTU service interval (5 to 10 

years) has been reached.

The CTU must be replaced.

Two red blinks Connection Hub has lost 

connection with the CTU. The CTU 

has been removed or the cable is 

damaged.

Replace the CTU and/or 

cable if necessary.

Three red 

blinks

The CTU has been emptied because 

of a fire alarm.

The CTU must be replaced.

OUTPUT signals 

AUX1 

state

AUX2 

state

Safera system status

OFF

OFF

Nothing to report: no active cooking or dangerous situation 

detected.

OFF

ON

Normal cooking detected.

ON

OFF

Alarm (dangerous situation detected: cooking hazard or 

water leakage).

ON

ON

Alarm (fire detected and liquid extinguish triggered).

3. AUX-connection to an Automation or 

Security System

The AUX signals can be interpreted in many ways:

1.  Simple ON/OFF information for any type of alarm (heat, fire or water leak). This 

can be read directly from AUX1 output. 

2.  Simple ON/OFF information for cooking activity. This can be read directly from 

AUX2 output.

3.  Simple ON/OFF information for fire extinguishing activity. This can be read 

directly when both AUX1 and AUX2 are connected in series to the same line.

4.  Four-state output according to the table below. This can be used by reading both 

AUX1 and AUX2 separately into the automation system and using internal logic 

to decide the state.

Содержание Connection Hub

Страница 1: ...1 20863_01 A User manual Safera Connection Hub for Safera Siro IN line and Siro R ...

Страница 2: ... galvanic connection between the Safera system and the automation system When the AUX outputs are active ON the optoisolator s output transistors will be held in conducting mode thus enabling current flow from IN to OUT This connection can be used exactly as a relay s contact however the direction and amount of the current flow must be controlled as specified below Maximum IN OUT voltage is 24 VDC...

Страница 3: ...ecurity System 3 24 VDC provided by the automation system Pull up recommended to provide 1mA absolute max 10mA Logic input of the automation system Signal ground of the automation system IN OUT SAFERA Example connection of one AUX output In this case the home automation system s logic input is pulled to ground potential when the AUX output signal is active Note that the maximum current pass in the...

Страница 4: ...reliable extinguish launch The Power Supply must be replaced One red blink The CTU service interval 5 to 10 years has been reached The CTU must be replaced Two red blinks Connection Hub has lost connection with the CTU The CTU has been removed or the cable is damaged Replace the CTU and or cable if necessary Three red blinks The CTU has been emptied because of a fire alarm The CTU must be replaced...

Страница 5: ...s and hold the child proof lock button To activate AUX2 cooking on press and hold the OK button 3 When you have finished testing press the adjustment mode button and pair the sensor unit again with the PCU normally according to the installation manual 5 Removing the Connection Hub or CTU from a Safera System Connection Hub and CTU cannot be removed by normal means The system s oper ating principle...

Отзывы: