1. Connection Hub Specifications

Safera Connection Hub enables two extra features for Safera Stove Guards:

1.  Auxiliary ON/OFF output with two signals and four states.

These signals are called AUX1 and AUX2. They can be used to send real-time 

status information to a building automation system. They operate with optoisola-

tors and thus provide a potential-free contact which is naturally compatible with 

almost all automation and security systems.

2.  Container Unit (CTU) connection for the optional liquid extinguishing system. 

This applies only to systems fitted with the necessary tubing and nozzles (Safera 

Siro IN-Line).

Electrical specifications

•  AUX outputs are optoisolated, thus there is no galvanic connection between the 

Safera system and the automation system.

•  When the AUX outputs are active (ON), the optoisolator’s output transistors will 

be held in conducting mode, thus enabling current flow from IN to OUT. This 

connection can be used exactly as a relay’s contact, however the direction and 

amount of the current flow must be controlled as specified below.

•  Maximum IN-OUT voltage is 24 VDC.

•  Maximum IN-OUT current is 10 mA.

•  Only DC voltage between IN-OUT, no AC is permitted!

AUX

IN 1 

= Yellow

OUT 1  = Green

IN 2  

= White

OUT 2   = Brown

Dimensions

110 x 55 x 22 mm

Power OUT

(Safera Siro IN-line or Siro R sensor unit)

CTU

Optional 

extinguisher unit

Power IN

(Safera Power 

Supply)

Content

1.  Specifications

2.  Connection to Safera system

3.  AUX-connection to Automation or Security system

4.  Installation and testing with Safera Siro and Siro R

5.  Removing the Connection hub or CTU from Safera system

Содержание Connection Hub

Страница 1: ...1 20863_01 A User manual Safera Connection Hub for Safera Siro IN line and Siro R ...

Страница 2: ... galvanic connection between the Safera system and the automation system When the AUX outputs are active ON the optoisolator s output transistors will be held in conducting mode thus enabling current flow from IN to OUT This connection can be used exactly as a relay s contact however the direction and amount of the current flow must be controlled as specified below Maximum IN OUT voltage is 24 VDC...

Страница 3: ...ecurity System 3 24 VDC provided by the automation system Pull up recommended to provide 1mA absolute max 10mA Logic input of the automation system Signal ground of the automation system IN OUT SAFERA Example connection of one AUX output In this case the home automation system s logic input is pulled to ground potential when the AUX output signal is active Note that the maximum current pass in the...

Страница 4: ...reliable extinguish launch The Power Supply must be replaced One red blink The CTU service interval 5 to 10 years has been reached The CTU must be replaced Two red blinks Connection Hub has lost connection with the CTU The CTU has been removed or the cable is damaged Replace the CTU and or cable if necessary Three red blinks The CTU has been emptied because of a fire alarm The CTU must be replaced...

Страница 5: ...s and hold the child proof lock button To activate AUX2 cooking on press and hold the OK button 3 When you have finished testing press the adjustment mode button and pair the sensor unit again with the PCU normally according to the installation manual 5 Removing the Connection Hub or CTU from a Safera System Connection Hub and CTU cannot be removed by normal means The system s oper ating principle...

Отзывы: