14
SafeLine GL6 v.2.1.1 EN
•
System failure
The output relay is activated when the GL6 has a GSM network.
The output relay is deactivated when the GSM network has
been lost for more than 15 seconds, or when the power has
been off for more than 15 minutes.
•
Emergency light
Relay is activated when there is a main power failure, and
switches to battery power.
4. Text message
Here you can enter information and specify the destination of the
text message.
•
Battery failure SMS
If the battery test fails, a text message is sent.
SMS destination: you can enter up to 3 mobile phone
numbers.
Message: the limit for the message text is 128 characters
maximum. E.g.: “The battery test has failed at...”
•
Mains failure SMS
A text message is sent if the 230 VAC supply has been lost for
more than 15 minutes.
SMS destination: you can enter up to 3 mobile phone
numbers.
Message: the limit for the message text is 128 characters
maximum.