background image

14

SAFETRON 6100, 6200, 6300 

 

Recommended strike plate placement for motor locks 6100 and 6200 is measured from the under side 

of the lock face plate and strike plate: 7,00mm +5,5mm -2,5mm

Recommended strike plate placement for motor lock 6300 is measured from the under side of the lock 

face plate and strike plate: 7,00mm +5,5mm -2,5mm 7mm +/- 3mm

 12,50 Max 

 5,50 Min 

 245 

 10 

 156 

 34,50 

 75 

 3 

 34,50 

 200 

 31 

 53 

 3 

 31 

 163 

6000 Narrow style

CL

CL

     SAFETRON 6100/6200 

       SAFETRON 6100/6200 

               SAFETRON 6300

ADJUSTING LATCH BOLT  (6200)

STRIKE PLATE OFFSET PLACEMENT

Содержание CU2

Страница 1: ...CONTROL UNIT CU2 Instruction manual 20211129 ...

Страница 2: ...ecting two motor lock 8 Terminal description 9 Replacing units 9 Activating re entry mode 9 Menu items 10 12 Error log 13 Warnings log 13 Accessories 13 Strike plate placement 14 Adjusting latch bolt 6200 6600 14 Installation of lock case 6100 6500 15 Installation of lock case 6200 6600 16 Installation of lock case 6300 17 Cut out drawings 18 Maintenance of motor locks 19 CONTENTS ...

Страница 3: ... strike plate model is suitable for the intended door see product catalog Installation method does not differ between different types of doors type wood metal SAFETRON motor lock is not intended for use on double action doors revolving door Established fixing instructions must be followed carefully during installation These instructions and any maintenance instructions must be passed on by the ins...

Страница 4: ...ating element Type of operation 3 7 6 1 1 3 5 2 A Emergency exit device 795 and 796 meets following requirement according to SS EN 179 2008 1 2 3 4 5 6 7 8 9 Category of use Durability and load on latch bolt Door mass and closing force Suitability for use on fire smoke doors Safety Corrosion re sistance and temperature Security and drill resistance Security electrical function Security electrical ...

Страница 5: ... or other blocking elements reaches full locked position NOTICE All components of the lock unit lockcase strikeplate and reinforcing plate must have the same classi fication according to SSF 3522 CALCULATION OF CABLE DIMENSIONS SSF 3522 Read and follow the installationmanual Motor lock should be used primarily electronically for best function Service like tex adjustment and lubricate shall be made...

Страница 6: ...6 OK Anslutning Lås 2 LOCK 2 TERMINAL LAYOUT ...

Страница 7: ...ct the lock case to the control unit via the terminal block on the back of the lock case The cable is then connected to terminal block LOCK COM on the control unit where power supply and communication A and B are found Correspond wires to the correct position on both lock case and control unit The terminal block on the lock case has an self locking mechanism but can be assisted through pressing do...

Страница 8: ... RELAY OUTPUTS Both motor locks has each seperate relay output on their designated outputs section Lock 1 1 2 Bolt out Activated when the bolt is out in the locked position 3 4 Bolt in Activated when the bolt is in in the unlocked position 5 6 Door open Controlled through the built in magnetic door sensor 7 8 Door closed Controlled through the built in magnetic door sensor 9 10 Impuls Closes the c...

Страница 9: ...osition 5 6 Door open Controlled through the built in magnetic door sensor 7 8 Door closed Controlled through the built in magnetic door sensor 9 10 Impuls Closes the circuit upon activation eg electric strikes 11 12 Alarm Activated when the bolt is blocked or door is open 13 14 Bolt out lock 2 Activated when the bolt is out in the locked position 15 16 Bolt in lock 2 Activated when the bolt is in...

Страница 10: ...timer lock 1 Open Tmr 4s 0 30s Bolt Dly 1 5s 0 5 5 0s ManL Dly 0s 0 30s Door Lrm 0s 10 120s Open Tmr Open time from activation until re lock Bolt Dly Time delay from when the door has been closed until the bolt is locked M Un Dly Time delay from when the lock is manually unlocked using key or thumb turn Door Lrm Door alarm for open door Factory setting is 0s which means inactive alarm 5 Lock2 time...

Страница 11: ...ivated when the bolt is blocked Errors Relay is activated when there are error codes Warnings Relay is activated when there are warnings DoorLarm Relay is activated when door is held open longer than specified time in Door Lrm in menu 4 and 5 Openers Automatic door openers function relay is activated upon activation and when the bolt is unlocked Vital C Vital closed relay is activated when door is...

Страница 12: ... lock 2 17 CU2 info1 S N F W H W M N S N Serial number on the control unit F W Firmware on the control unit H W Hardware version on the control unit M N Model number on the control unit 18 CU2 info2 M D I D M D Manufacturing date of the unit I D Installation date of the unit auto set 12h after install 19 CU2 environ VDC Rh C Runtime VDC Incoming voltage on the control unit Rh Current humidity on t...

Страница 13: ...d above 90 25 Low temperature Triggered below 20 C 26 High temperature Triggered above 70 C NO ERROR DESCRIPTION 31 Bolt blocked Id is the adress of lock case 32 Door larm Door open longer than set max time 33 Manipulation Bolt manipulation Triggered when bolt looses in out status WARNING LOG MENU 22 ACCESSORIES Description Art no Strikeplate 106 1 12 5 mm 202 144 753 Strikeplate 106 2 15 mm 202 1...

Страница 14: ...0mm 5 5mm 2 5mm Recommended strike plate placement for motor lock 6300 is measured from the under side of the lock face plate and strike plate 7 00mm 5 5mm 2 5mm 7mm 3mm 12 50 Max 5 50 Min 245 10 156 34 50 75 3 34 50 200 31 53 3 31 163 6000 Narrow style C L C L SAFETRON 6100 6200 SAFETRON 6100 6200 SAFETRON 6300 ADJUSTING LATCH BOLT 6200 STRIKE PLATE OFFSET PLACEMENT ...

Страница 15: ...SAFETRON 6100 50 20 42 42 111 170 R11 22 225 200 R16 50 4 140 28 40 27 15 INSTALLATION OF LOCK CASE ...

Страница 16: ...50 20 42 42 111 170 R11 22 225 200 R16 50 4 140 28 40 27 8 RUBRIK SAFETRON 6200 16 INSTALLATION OF LOCK CASE ...

Страница 17: ...8 RUBRIK SAFETRON 6300 220 23 138 41 30 176 59 26 35 13 50 20 16 6 58 120 50 10 17 INSTALLATION OF LOCK CASE ...

Страница 18: ...4 R11 165 Lock case height 156 20 50 11 Cable in and output C L Required only for locks with latchbolt SAFETRON 6300 225 3 25 58 Lock case depth 53 35 16 132 50 57 6 10 70 26 59 12 R5 203 4 20 175 Lock case height 163 25 R12 50 Cylinder C L Cable in and output 18 CUT OUT DRAWINGS ...

Страница 19: ...nts as necessary In normal use lubricate the lock housing mechanical parts once a year Use a lubricant that does not contain graphite or solvents At high frequency use lubricate mechanical parts as needed Lock housing electrical components are maintenance free Check that the door closes properly If necessary adjust door hinges and or door closers A bad door function adversely affects locking ...

Страница 20: ...Box 2096 65002 Karlstad Sweden Rätt till ändringar av katalogens innehåll och sortiment förbehålls Vi reserverar oss för eventuella tryckfel SAFETRON är ett registrerat varumärke Tel 46 54 19 02 45 info safetron com www safetron com ...

Отзывы: