Model 70-742-R-MS-KIT Wiring -
SPECIAL WIRING NOTICE:
When replacing CCI Controls LP Gas
Leak Detectors they may have two power leads. Safe-T-Alert units only
have one power lead. Simply connect the Safe-T-Alert power lead (Red) to
the coach/house power supply and cap or remove the other power lead.
DO
NOT CONNECT BOTH POWER LEADS TO THE Safe-T-Alert
ALARM – this will result in a dead chassis battery.
Only use UL or recognized permanent wire connectors to
replace any unit installed with spade connectors or wire nuts.
TEST PROCEDURE
!
WARNING
TO REDUCE THE RISK OF CARBON MONOXIDE POISONING
OR PROPANE GAS EXPLOSION, TEST THIS ALARM’S
OPERATION AFTER THE RV HAS BEEN IN STORAGE, BEFORE
EACH TRIP AND AT LEAST ONCE PER WEEK DURING USE BY
PRESSING THE TEST/RESET BUTTON
.
!
WARNING
WARNING: THE TEST BUTTON ONLY TESTS THE
ALARM CIRCUIT NOT THE SENSORS. YOU MAY USE
PROPANE OR BUTANE GAS TO TEST THE GAS SENSOR.
Note it may take up to 10 seconds for the alarm to sound.
TO TEST THE CO SENSOR USE A CAN OF SAFE-T-ALERT
CO TEST GAS TO TEST THE 400 PPM CALABRATION
POINT. DO NOT TRY TO GENERATE CO TO TEST THE
ALARM.
The TEST/RESET button tests all ELECTRICAL functions of
the alarm. It does not check the sensor operation.
The alarm may be tested at any time. The TEST/Mute switch is located on
the front of the alarm. Press and hold the test button for 1 second
IMPORTANT
-
If this alarm does not test properly return it immediately
for repair or replacement. If the alarm is over five years old replace it.
OPERATION
When the unit is first powered up, the CO sensor requires a ten (10) minute
initial warm-up period to clean the sensor element and achieve stabilization.
The GREEN LED indicator will flash on and off during the 10 minute
warm-up period. This unit cannot go into a alarm during the warm-up
period. See Test Procedure in this manual. After the warm-up period, the
GREEN power ON indicator should glow continuously
If the ON indicator
light does not light, see the section,
Trouble-Shooting Guide
, in this
manual for further information.
Do not attempt to fix it yourself.
Gas Alarm:
When you power the alarm, it has a warm-up period of
approximately 1 minute. This unit cannot go into a gas alarm during the
warm-up period. After 1 minute the alarm can detect explosive gas and will
energize the relay on models 70-742-R Kit and 70-742-R-MS Kit.
Simultaneous CO and Gas Alarms—
Because the risk of a propane gas
explosion is generally a more serious danger, your alarm unit gives the gas
alarm a higher priority during simultaneous alarm condition.
If your unit generates alarms for both Gas and CO at the same time, the gas
LED will flash red and the beeper will sound. The CO LED will be a solid
Red until the CO is ventilated out of the RV, at which time the LED will
return to the Green operational/safe color.
Brownout Protection -
The unit can tolerate short power interruptions and
brownouts where the circuit voltage drops as low as 1 VDC. If the brownout
lasts too long, the unit will reset and operate as described above.
LOW POWER OPERATION
This alarm will operate normally down to7 VDC. Do not operate this alarm
below 7 VDC.
VISUAL AND AUDIBLE ALARM SIGNALS
This SAFE-T-ALERT
TM
CO / Propane Gas Alarm is designed to be easy-
to-operate. The alarm has two indicator lights that display a specific color
for each monitored condition. There also is a matching sound pattern for
alarm conditions.
CO ALARM
The Red CO LED will flash and the alarm will sound 4 “BEEPS” then
silent for 5 Seconds
.
These signals
indicates that the CO level is over 70
ppm.
IMMEDIATE ACTION IS REQUIRED.
See
Procedures To Take
During An Alarm
. This cycle will continue until the TEST/Mute button on
the front of alarm is pressed. Ventilate the RV. The RED light will stay ON
until the CO has cleared, or the alarm will reactivate in approximately 6
minutes if the CO is still present. DO NOT RE-ENTER THE RV. This
alarm will return to normal operation after the RV s properly ventilated.
PROPANE GAS ALARM
The Red LED will Flash and the alarm will sound a steady tone whenever a
dangerous level of propane or methane gas is detected.
IMMEDIATE
ACTION IS REQUIRED.
See
Procedures Take During A Gas Alarm
The detector will continue to alarm until the Test/Mute switch on the front
of the alarm is pressed. Ventilate the RV. The RED Gas LED will continue
to flash until the gas has cleared, or the gas alarm will reactivate in
approximately 5 minutes if the gas is still present. DO NOT RE-ENTER
THE RV. This alarm will return to normal operation after the RV s properly
ventilated.
MALFUNCTION/SERVICE SIGNAL
If any malfunction is detected, the
Gas LED will remain off and the Operational/CO LED will alternate
Red/Green and the alarm will sound once every 15 seconds. Press the
Test/Mute button. If the Test/Mute button does not clear the signals, check
the battery voltage. I
f the battery voltage is not low and the unit will not
return to normal operation,
immediately remove the alarm and return
for service or warranty replacement.
See the warranty section in this
manual.
OPERATION
NORMAL
CO ALARM
PROPANE ALARM
ALARM
MALFUNCTION
END OF LIFE
SIGNAL
AUDIBLE SIGNAL VISUAL SIGNAL
NONE STEADY GREEN
4 “BEEPS” STEADY RED
5 SECONDS OFF
5
“ CONSTANT FLASHING RED
“ BEEP” EVERY ALTERNATING
25 SECONDS RED/GREEN
F
A BEEPS EVERY RED RED GREEN GREEN
25-30 SECONDS FLASHING