SAFE-T-ALERT 70-742 Скачать руководство пользователя страница 3

 

INSTALLATION INSTRUCTIONS 

 

Follow these instructions carefully. Failure to follow these instructions can 
damage the unit and void the warranty. 

 

Important: The 70 Series case requires 1 1/2” (38mm) clearance.  
 
MODEL  70-742  

1.

 

Basic Model 70-742

 - Select a wall location between 4” and 20” off the 

floor.  Cut a 5 5/8” (143mm) W x 3 1/8” (79mm) H hole.  

2.

 

Connect Supply (+) to the Red wire lead.  Install a 1 amp fuse in the 
positive (+) circuit. Connect the Black wire to the 12 volt Ground (-). 

3.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm. 

 

 

 
MODEL  70-742-R KIT    

1.

 

Model 70-742-R Kit - With Normally Closed relay.

 This unit supplies 

a relay with contacts rated 12 VDC, 3 amp (max). The relay is energized 
whenever the alarm is operational. It may be used to shut down a 
generator or to open an (optional) gas solenoid valve. The relay may also 
be used to interface to alarm systems, using either the normally closed or 
normally open contact, depending on the requirements of the alarm 
system. In the event of an alarm the relay will shut off.  It will 
automatically energize after the unsafe levels of CO or explosive gas 
clears.  
Select a wall location between 4” and 20” off the floor. Cut a 5 5/8” 
(143mm) W x 3 1/8” (79mm) H hole. 

2.

 

 Mount the solenoid according to its separate instructions. You must 
install the solenoid included with the 70-742-R Kit

. Do not connect 

to an existing installed solenoid.

 

SEE: SPECIAL WIRING 

NOTICE. 

Connect the Red wire and either White wire from the alarm to 

the 12 volt supply (+). Install a 5 amp fuse in the positive (+) circuit 
between this connection and the battery.  
Connect the Black wire to the 12 volt Ground (-). 

3.

 

Relay Output – Connect the remaining White wire from the alarm to 
either black wire from the solenoid. 
 Ground the remaining Black wire from the solenoid to the negative side 
(-) of the 12 volt battery OR ground it to the RV Chassis.  
Note: Some devices do not require correct polarity and can be connected 
to either terminal or wire. 

4.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm. 

 

 

 

 

 

 

 

 

 

 

 
MODEL  70-742-MS

 

1.

 

Model 70-742-MS Multi-station interconnect

(Maximum 10 units 

and 2000 feet of wire)

. Allows multiple 70-742-MS alarms to be 

connected together.  When one of the alarms detects unsafe levels of CO 
or gas it will activate.  It will also activate the audible alarm of all the 
interconnected units.  Only the alarm that detected CO or gas will have 
its Red LED light lit up so that you can determine the cause of the 
alarm.   Select a wall location no between 4” and 20” off the floor. Cut a 
5 5/8” (143mm) W x 3 1/8” (79mm) H hole. 

2.

 

 Connect the Red wire to the 12 volt supply (+). Install a 1 amp fuse in 
the positive circuit (+). 

Note you must use a separate 1 amp fuse for 

each alarm.  

Connect the Black wire to the 12 volt Ground (-). 

3.

 

Interconnect Wiring – Connect Blue wires from each alarm and Yellow 
wires for each alarm. Continue connecting in series (Daisy Chain). 

4.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm. 

 

 

 

MODEL 70-742-R-MS KIT  

1.

 

Model 70-742-R-MS Kit - With Normally Closed relay.

 This unit 

supplies a relay with contacts rated12 VDC, 3 amp (max). The relay is 
energized whenever the alarm is operational. It may be used to shut 
down a generator or to open an (optional) gas solenoid valve. The relay 
may also be used to interface to alarm systems, using either the 
normally closed or normally open contact, depending on the 
requirements of the alarm system. In the event of an alarm the relay 
will shut off.  It will automatically energize after the unsafe levels of 
CO or gas clears.  
 Select a wall location between 4” and 20” off the floor. Cut a 5 5/8” 
(143mm) W x 3 1/8” (79mm) H hole. 

2.

 

Mount the solenoid according to its separate instructions. You 
must install the solenoid included with the 70-742-R-MS KIT. 

Do 

not connect to an existing installed solenoid.

 

SEE: SPECIAL 

WIRING NOTICE. 

Connect the Red wire and either White wire from 

the alarm to the 12 volt supply (+). Install a 5 amp fuse in the positive 
(+) circuit between this connection and the battery. 

Note you must use 

a separate 5 amp fuse for each alarm. 

Connect the Black wire to the 

12 volt Ground (-). 

3.

 

Relay Output – Connect the remaining White wire from the alarm to 
either black wire from the solenoid.  Ground the remaining Black wire 
from the solenoid to the negative side (-) of the 12 volt battery OR 
ground it to the RV Chassis.  
Note: Some devices do not require correct polarity and can be 
connected to either terminal or wire. 

4.

 

Interconnect Wiring - Connect Blue wires from each alarm and Yellow 
wires from each alarm. Continue connecting in series (Daisy Chain).

 

5.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm.

 

 

 

 

 

!

 DANAGER - FIRE RISK - CCI CONTROLS GAS LEAK DETECTOR REPLACEMENT   

      - DO NOT CONNECT A SAFE-T-ALERT alarm to non Safe-T-Alert supplied solenoid. You must 

use the new solenoid included in your Kit.  DO NOT CONNECT TO A CCI SOLENOID. 

 

Отзывы: