background image

Connect  to  wiring  or  circuit  that  CANNOT  be  turned  off  by  a 
switch  or  ground  fault  protector.  Only  use  UL  or  recognized 
permanent  wire  connectors. 

It  is  acceptable  to  connect  the  35 

Series CO / LP gas alarm to the main disconnect. The alarm will be 
off along with all other 12 volt equipment when the main disconnect 
is turned to the off position. The RV must not be occupied when the 
main disconnect is in the off position. 

INSTALLATION INSTRUCTIONS 

 

Follow these instructions carefully. Failure to follow these instructions can 
damage the unit and void the warranty. 
Select a wall location at least 4” but not more than 20” off the floor. 

1.

 

Disconnect the power supply being connected to. 

2.

 

Model  35-741  requires  a  1/2”  hole  be  drilled  where  mounting. 
Model 35-742 requires a 1” clearance to recess the case. Cut a

 

3/8” W x 2” H

 

hole 

3.

 

C

onnect  the  RED  (+)  power  lead  to  the  fused  circuit.  Connect 

the BLACK lead to Ground (-).  

4.

 

Fasten the unit to the wall using the two screw holes located on 
the ends of the case  

5.

 

Reconnect the power supply. Wait 10 minutes for warm up and 
then test the alarm.

 

 

NOTE:  All  connections  must  be  in  accordance  with  the  National 
Electrical Code in the Unites Stated and the Canadian Electric Code in 
Canada . 

 

TEST PROCEDURE

 

!

 WARNING 

TO  REDUCE  THE  RISK  OF  CARBON  MONOXIDE  POISONING 
OR  PROPANE  GAS  EXPLOSION,  TEST  THIS  ALARM’S 
OPERATION AFTER THE RV HAS BEEN IN STORAGE, BEFORE 
EACH TRIP AND AT LEAST ONCE PER WEEK DURING USE

!

 

WARNING 

WARNING:  THE  TEST  BUTTON  ONLY  TESTS  THE 
ALARM  CIRCUIT  NOT  THE  SENSORS.  YOU  MAY  USE 
PROPANE OR BUTANE GAS TO TEST THE GAS SENSOR. 
Note it may take up to 10 seconds for the alarm to sound. 
TO TEST THE CO SENSOR USE A CAN OF SAFE-T-ALERT 
CO  TEST  GAS  TO  TEST  THE  400  PPM  CALABRATION 
POINT.  DO  NOT  TRY  TO  GENERATE  CO  TO  TEST  THE 
ALARM.

  The TEST/RESET button tests all ELECTRICAL functions of 

the alarm. It does not check the sensor operation. 

The alarm may be tested at any time -The TEST/Mute switch is located on 
the front of the alarm Press and hold the test button for 1 second.  The alarm 
is working properly if the GREEN indicator light changes color to RED and 
the horn beeps 4 times. The Gas LED should also blink Red. 

IMPORTANT

 - 

 If this alarm does not test properly return it immediately 

for repair or replacement. 

 

OPERATION

 

 Each  time  the  unit  is  first  powered  up,  the  CO  sensor  requires  a  ten  (10) 
minute  initial  warm-up  period  to  clean  the  sensor  element  and  achieve 
stabilization. The GREEN LED indicator will flash on and off during the 10 
minute  warm-up  period.  This  unit  cannot  go  into  a  CO  alarm  during  the 
warm-up period.  To test your unit during the warm-up period, press the test 
button.  See  Test  Procedure  in  this  manual.    After  the  warm-up  period,  the 
GREEN power ON indicator should glow continuously

 

If the ON indicator 

light  does  not  light,  see  the  section, 

Trouble-Shooting  Guide

,  in  this 

manual for further information.  

Do not attempt to fix it yourself. 

Gas  Alarm: 

When  you  power  the  alarm,  it  has  a  warm-up  period  of 

approximately  1  minute.  This  unit  cannot  go  into  a  gas  alarm  during  the 
warm-up period.  After 1 minute the alarm can detect explosive gas.  

Simultaneous  CO  and  Gas  Alarms—

  Because  the  risk  of  a  propane  gas 

explosion is generally a more serious danger, your alarm unit gives the gas 
alarm a higher priority during simultaneous alarm condition.

 

If your unit generates alarms for both Gas and CO at the same time, the gas 
LED  will flash red and the beeper will sound.  The CO LED will be a solid 
Red  until  the  CO  is  ventilated  out  of  the  RV,  at  which  time  the  LED  will 
return to the Green operational/safe color.   

Brownout Protection - 

The unit can tolerate short power interruptions and 

brownouts where the circuit voltage drops as low as 1VDC. If the brownout 
lasts too long, the unit will reset and operate as described above. 

 

LOW POWER OPERATION 

This alarm will operate normally down to7 VDC.  Do not operate this alarm 
below 7 VDC.  

 

VISUAL AND AUDIBLE ALARM SIGNALS 

This  SAFE-T-ALERT

TM

 

CO  /  Propane  Gas  Alarm  is  designed  to  be  easy-

to-operate.  The  alarm  has  two  indicator  lights  that  display  a  specific  color 
for  each  monitored  condition.  There  also  is  a  matching  sound  pattern  for 
alarm conditions. 

 

CO ALARM 

The  Red  CO  LED  will  flash  and  the  alarm  will  sound  4  “BEEPS”  then 
silent  for  5  Seconds

.   

These  signals

 

indicate  that  the  CO  level  is  over  35 

ppm.

 IMMEDIATE ACTION IS REQUIRED. 

See 

Procedures To Take 

During An Alarm

. This cycle will continue until the TEST/Mute button on 

the front of alarm is pressed. Ventilate the RV. The RED light will stay ON 
until  the  CO  has  cleared,  or  the  alarm  will  reactivate  in  approximately  6 
minutes  if  the  CO  is  still  present.  DO  NOT  RE-ENTER  THE  RV.  This 
alarm will return to normal operation after the RV s properly ventilated. 

 

PROPANE GAS ALARM 

The Red LED will Flash and the alarm will sound a steady tone whenever a 
dangerous  level  of  propane  gas  is  detected. 

IMMEDIATE  ACTION  IS 

REQUIRED. 

See 

Procedures  Take  During  A  Gas  Alarm

  The  detector 

will continue to alarm until the Test/Mute switch on the front of the alarm is 
pressed.  Ventilate  the  RV.  The  RED  Gas  LED  will  continue  to  flash  until 
the  gas  has  cleared,  or  the  gas  alarm  will  reactivate  in  approximately  5 
minutes  if  the  gas  is  still  present.  DO  NOT  RE-ENTER  THE  RV.  This 
alarm will return to normal operation after the RV s properly ventilated. 

 

MALFUNCTION/SERVICE SIGNAL 

If any malfunction is detected, the 

Gas  LED  will  remain  off  and  the  Operational/CO  LED  will  alternate 
Red/Green  and  the  alarm  will  sound  once  every  15  seconds.  Press  the 
Test/Mute button. If the Test/Mute button does not clear the signals, check 
the battery voltage. I

f the battery voltage is not low and the unit will not 

return to normal operation,

 

immediately remove the alarm and return 

for  service  or  warranty  replacement.

  See  the  warranty  section  in  this 

manual. 

 

   

OPERATION 

  

 

  NORMAL 

 

 

  CO ALARM 
    

 

  

  PROPANE ALARM 

  

  ALARM  
  MALFUNCTION 
 
  END OF LIFE    

     

AUDIBLE SIGNAL        VISUAL SIGNAL

  

 

                                       

        NONE                    STEADY  GREEN 

   

   

  

 

      

4 “BEEPS”                  STEADY RED 

      5 SECONDS OFF 

 

 

“   CONSTANT                 FLASHING RED 

   

  

“    BEEP” EVERY             ALTERNATING 

   30 SECONDS              RED/GREEN 

 
B   BEEPS EVERY           RED RED GREEN GREEN   
     25-30 SECONDS              FLASHING   

 

Отзывы: