WFDTNA Vane-type Water flow Detectors

INSTALLATION  AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Contact Ratings: 

Two sets of SPDT (Form C); 10 A @ 125/250 VAC 

; 2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 – 10 GPM

Static Pressure Rating: 

375 PSI (Max.)

Dimensions, Installed: 

WFDTNA – 4in H x 3½

 

in W x 6¾ in D

Operating Temperature Range: 

32°F to 120°F (0°C to 49°C)

Enclosure Rating: 

WFDTNA – NEMA Type 4, as tested by Underwriters Laboratories, Inc. (UL) (IP56)

The WFDTN can be installed between 2×4 stud wall construction.

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of water flow detectors. Purchasers who install water flow detectors for use 

by others must leave this manual or a copy of it with the user. Read all instructions 

carefully before beginning.

CAUTION

The model WFDTNA is a vane-type water flow detector for use in wet-pipe fire sprin-

kler systems only. Vane-type water flow detectors shall not be used as the sole initiat-

ing device in both deluge and preaction systems; water flow detectors used in these 

types of systems may result in an unintended discharge caused by a surge, trapped air 

or a short retard time. 

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type water flow detectors mount to water filled pipes in fire sprinkler systems. 

Water flow in the pipe deflects a vane. Deflection of the vane produces a switched 

output, usually after a specified delay.
All WFDTNAs have a pneumatically controlled mechanical delay mechanism. Delays 

do NOT accumulate; they reset if the flow of water stops or drops below minimum 

triggering flow rate before the entire delay has elapsed. All detectors will activate on 

a sustained flow of water of 10 gallons per minute (gpm) or greater downstream of 

the device.

COMPATIBLE PIPE TEES/RISERS

The WFDTNA is supplied with 12 paddles. One paddle is provided for each size of 

the threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart. Each 

paddle has an indication that shows the pipe size and type of tee to be used with. The 

WFDTNA also fits 1", 1½", and 2" Reliable riser manifolds when used with paddle 

tree P02-0032-300 (purchased separately). 

APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)

Tee Depth

Threaded

Sweat

CPVC

CPVC/Spears/

NIBBCO

CPVC/Tyco/NIBBCO

1 × 1 × 1˝

2

1

/

8

˝

1

3

/

4

˝

2

1

/

4

˝

2

15

/

32

˝

2

13

/

16

˝

1

1

/

4

 × 1

1

/

4

 × 1˝

2

1

/

2

˝

2

1

/

8

˝

N/A

N/A

N/A

1

1

/

2

 × 1

1

/

2

 × 1˝

2

3

/

4

˝

2

1

/

4

˝

N/A

N/A

N/A

2 × 2 × 1˝

3

1

/

4

˝

2

3

/

4

˝

N/A

N/A

N/A

FIGURE 1. MOUNTING DIMENSIONS:

3-1/2"

2-5/8"

4"

TEE DEPTH

DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION

PLASTIC VANE

TEE FITTING

INSTALLATION GAUGE

END OF PADDLE TREE MUST

FIT BETWEEN TOP OF TEE

AND BOTTOM OF FLANGE

TEE

ADAPTER

INSTALLATION GUIDELINES

Before installing any water flow alarm device, be thoroughly familiar with:
NFPA 72:  National Fire Alarm Code
NFPA 13:  Installation of Sprinkler Systems
NFPA 25:   Inspection, Testing, and Maintenance of Water-based Fire Protection 

Systems, Section 5.3.3.2

NFPA 13D:  Standard for 1 and 2 Family Dwellings and Manufactured Homes
NFPA 13R:  Standard for Multi-family Dwellings
CAN/ULC S524: Installation of Fire Alarm Systems
Also, follow other applicable NFPA and ULC standards, local codes and the require-

ments of the authority having jurisdiction.

W0390-00

Содержание WFDTNA

Страница 1: ...deflects a vane Deflection of the vane produces a switched output usually after a specified delay All WFDTNAs have a pneumatically controlled mechanical delay mechanism Delays do NOT accumulate they reset if the flow of water stops or drops below minimum triggering flow rate before the entire delay has elapsed All detectors will activate on a sustained flow of water of 10 gallons per minute gpm or...

Страница 2: ... is recommended Use height gage located at end of paddle tree to ensure proper depth of detector on tee fitting See Figure 1 Height gage must fit between top of tee fitting and under side of hex tee adapter A gap between gage and tee adapter is acceptable When correctly installed the detector must face in the proper direction of water flow and be aligned with the pipe the provided directional cove...

Страница 3: ... SECONDS NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS DELAY ADJUSTMENT DIAL W0385 00 MAINTENANCE To prevent accidental water damage control valves should be shut tightly and the sys tem completely drained before water flow detectors are removed or replaced Inspect detectors in accordance with applicable ULC codes and standards and or the authority having jurisdiction for leaks and replace i...

Страница 4: ...PS 24 VDC 2 5 AMPS ULC LISTED COMPATIBLE CONTROL PANEL POWER 24VDC OR 120VAC INITIATING LOOP SSM24 X SSV120 X NOTE COMMON AND B NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFLECTED I E WHEN WATER IS FLOWING DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR SCHEMATIC OF INDIVIDUAL SWITCH IN NO WATERFLOW CONDITION BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION DO NOT ALLOW STRIPPE...

Отзывы: