background image

MECHANICAL DELAY ADJUSTMENT

The pneumatic delay is preset at the factory to 30 seconds. To adjust the setting, turn 

the adjustment dial clockwise to increase the delay, counterclockwise to decrease it. 

The delay is adjustable from 0 to 90 seconds max. See Figure 5. As a point of refer-

ence when setting time delay in dark environments the notch in the dial indicates an 

approximate 30 second time delay and the larger of the three tabs indicates an ap-

proximate 60 second time delay.
NOTE: Set the delay to the minimum required to prevent false alarms from flow 

surges.
Periodically test time delay as required by Authority Having Jurisdiction or code au-

thority.

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, main-

taining, or testing waterflow alarm devices.
1.   Replace the cover and tighten the tamper proof screws with the tamper proof 

wrench. Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detector to 

indicate a flow condition. The detector should remain activated until the inspec-

tor’s test valve is closed. Air pockets in the sprinkler system may increase the 

apparent delay.

MAINTENANCE

To prevent accidental water damage, control valves should be shut tight and the sys-

tem completely drained before waterflow detectors are removed or replaced.
Inspect detectors in accordance with applicable NFPA codes and standards and/or the 

Authority Having Jurisdiction for leaks and replace if a leak occurs. Test detectors at 

least quarterly, as described under Operational Testing, to ensure proper operation. 

Test more often if required by the authority having jurisdiction.
Under normal conditions, Safe Signal waterflow detectors should provide years of 

trouble-free service. However, if the delay mechanism becomes faulty, a replacement 

kit is available. To replace the delay mechanism, request Part No. FS-RT. Complete 

instructions are enclosed with replacement parts. The mechanism can be easily re-

placed without removing the detector from the pipe or draining the pipe. Do not 

repair or replace any other waterflow detector components. If any other part of the 

detector does not perform properly, replace the entire detector. Installation methods 

other than those listed in this installation manual may prevent the device from re-

porting the flow of water in the event the associated sprinkler system is activated by 

a fire. Safe Signal is not responsible for devices that have been improperly installed, 

tested, or maintained.
To remove a detector:
1.  Drain the pipe.
2.  Turn off electrical power to the detector and disconnect the wiring.
3.  Loosen the nuts and remove the U-bolts.
4.   Gently lift the saddle far enough to get your fingers under it. Then, roll the vane 

so it will fit through the hole while continuing to lift the waterflow detector 

saddle.

5.  Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane may restrict 

the flow of water to all or part of the fire sprinkler system. 

FIGURE 4. KNOCKOUT PLUG REMOVAL

GROUND 

GROUND 

SCREW

SCREW

W0383-01

FIGURE 5. DELAY ADJUSTMENT DIAL:

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS

DELAY

ADJUSTMENT

DIAL

W0385-00

  

I56-4045-E 

 

 4/21

Содержание WFDN

Страница 1: ...ow Shipping Weight 3 to 6 lbs according to size Enclosure Rating NEMA Type 4 as tested by Underwriters Laboratories Inc U S Patent Numbers 5 213 205 CAUTION Do NOT use any of the WFDN models on copper pipe The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from func tioning properly Do NOT install steel or iron pipe sections in copper piping for mo...

Страница 2: ... drain the system and remove the detector refer to Maintenance Check for dirt or foreign objects under the gasket and make sure that the pipe surface is not dented Reinstall the detector and check again for leaks Do not proceed until all leaks have been stopped 2 Connect an ohmmeter or continuity tester across the COM and B NO switch terminals The ohmmeter should indicate an open circuit 3 Deflect...

Страница 3: ...rational Testing to ensure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the delay mechanism becomes faulty a replacement kit is available To replace the delay mechanism request Part No FS RT Complete instructions are enclosed with replacement parts Th...

Страница 4: ...ESTED EOL RESISTOR SSM24 X SSV120 X NOTE COMMON AND B NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFECTED I E WHEN WATER IS FLOWING DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR CONTACT RATINGS SCHEMATIC OF INDIVIDUAL SWITCH IN NO WATERFLOW CONDITION A NC COM B NO BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING ...

Отзывы: