background image

3.   Remove burrs and sharp edges from the hole. Clean and remove all scale and 

foreign matter from the inside of the pipe for a distance equal to the pipe diam-

eter on either side of the hole to ensure free movement of the vane. Clean the 

outside of the pipe to remove dirt, metal chips, and cutting lubricant.

4.   Seat the gasket against the saddle and mount the detector directly to the pipe. 

Carefully roll the vane opposite the direction of flow and insert it through the 

hole (see Figure 3). Seat the saddle firmly against the pipe so that the locating 

boss goes into the hole.

5.   Install the U-bolt, tightening the nuts alternately to ensure a uniform seal (see 

Table 1 for torque values).

6.   Remove the cover with the tamper-proof wrench provided. Move the actuator 

lever back and forth to check for binding. If the vane binds, remove the detector 

and correct the cause before proceeding.

CAUTION

Be sure the direction-of-flow arrow and directional cover point in the correct direc-

tion or else waterflow will go unreported. See Figure 3 and Figure 6.

FIGURE 1. MOUNTING DIMENSIONS

8.9 CM

(3.5")

6.6 CM

(2.6")

PIPE DIAMETER

PLUS 12.7 CM

(5")

PIPE

VANE

OVERALL WIDTH = PIPE DI 6.4 CM (2.5")

U-BOLT

NUT

PIPE

SADDLE

U-BOLT

PIPE

FIGURE 2. MOUNTING HOLE LOCATION

W RO NG

RIG HT

REM O VE BURRS FRO M  EDG E O F HO LE. CLEAN O UT SCALE

AND FO REIG N M ATTER FRO M  INSIDE W ALL O F PIPE.

W0106-00

TABLE 1.

WFDN MODEL

HOLE SIZE (IN)

TORQUE

20, 25

1

1

/

4

30–35 ft.-lb.

40

2

45–50 ft.-lb.

30, 50, 60, 80

2

60-65 ft.-lb

PRE-OPERATION TESTING 

1.   Fill the fire sprinkler system and check for leaks around the waterflow detector. 

If it leaks, first check for the proper torque on the U-bolt nuts. If the leak per-

sists, drain the system and remove the detector (refer to Maintenance). Check 

for dirt or foreign objects under the gasket, and make sure that the pipe surface 

is not dented. Reinstall the detector and check again for leaks. Do not proceed 

until all leaks have been stopped.

2.   Connect an ohmmeter or continuity tester across the COM and B-NO switch 

terminals. The ohmmeter should indicate an open circuit.

3.   Deflect the actuator lever and hold it until the pneumatic delay shaft releases the 

switch buttons. The ohmmeter or continuity tester should show a short circuit 

after the delay has elapsed. If there is no delay, check the setting of the delay 

adjustment dial.

FIGURE 3. ASSEMBLY DIAGRAM

WATERFL

OW

U-BOLT

PIPE

SADDLE GASKET

REFER TO

 TABLE 1

U-BOLT

NUT

ELECTRICAL

CONDUIT

ENTRANCE

COVER

TAMPER PROOF

WRENCH

(P/N WFDW)

ROLL PADDLE

OPPOSITE OF

FLOW ARROW

WHILE INSERTING

PIPE SADDLE

MOUNTING PLATE

TIMER

(REPLACEMENT

P/N FS-RT)

COVER TAMPER

SWITCH

(OPTIONAL P/N CTS)

W0392-00

FIELD WIRING

1.    All models have two SPDT switches. Switch contacts COM and B-NO are closed 

when water is flowing and open when it is not. Connect the switches, as shown 

in Figure 7, depending on the application.

2.    When connected to a listed fire sprinkler/fire alarm control panel, the initiating 

circuit must be unable to be silenced.

3.    A ground screw is provided with all waterflow detectors. When grounding is 

required, clamp wire with screw in hole located between conduit entrance holes. 

See Figure 4.

4.  Use proper waterproof conduit fittings where required.

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device 

to which AC power is applied. Doing so may result in injury or death.

When utilizing switches at voltages greater than 74VDC 

 or 49VAC 

 

means to provide all–pole disconnection must be incorporated in the fixed wiring, 

such as a circuit breaker.

W0384-00

  

I56-4045-E 

 

 4/21

Содержание WFDN

Страница 1: ...ow Shipping Weight 3 to 6 lbs according to size Enclosure Rating NEMA Type 4 as tested by Underwriters Laboratories Inc U S Patent Numbers 5 213 205 CAUTION Do NOT use any of the WFDN models on copper pipe The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from func tioning properly Do NOT install steel or iron pipe sections in copper piping for mo...

Страница 2: ... drain the system and remove the detector refer to Maintenance Check for dirt or foreign objects under the gasket and make sure that the pipe surface is not dented Reinstall the detector and check again for leaks Do not proceed until all leaks have been stopped 2 Connect an ohmmeter or continuity tester across the COM and B NO switch terminals The ohmmeter should indicate an open circuit 3 Deflect...

Страница 3: ...rational Testing to ensure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the delay mechanism becomes faulty a replacement kit is available To replace the delay mechanism request Part No FS RT Complete instructions are enclosed with replacement parts Th...

Страница 4: ...ESTED EOL RESISTOR SSM24 X SSV120 X NOTE COMMON AND B NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFECTED I E WHEN WATER IS FLOWING DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR CONTACT RATINGS SCHEMATIC OF INDIVIDUAL SWITCH IN NO WATERFLOW CONDITION A NC COM B NO BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING ...

Отзывы: